Spesifikasi CP1H

General Specifications

TypeAC power supply modelsDC power supply models
ModelCP1H-[][][]-ACP1H-[][][]-D
Power supply100 to 240 VAC 50/60 Hz24 VDC
Operating voltage range85 264 VAC20.4 to 26.4 VDC 
(with 4 or more Expansion Units and 
Expansion I/O Units: 21.6 to 26.4 VDC)
Power consumption100 VA max. (CP1H-[][][]-A)50 W max. (CP1H-[][][]-D)
Inrush current *100 to 120 VAC inputs: 
20 A max. (for cold start at room 
temperature) 
8 ms max. 
200 to 240 VAC inputs: 
40 A max. (for cold start at room 
temperature), 
8 ms max.
30 A max. (for cold start at room 
temperature) 
20 ms max.
External power supply300 mA at 24 VDCNone
Insulation resistance20 MΩ min. (at 500 VDC) between the 
external AC terminals and GR terminals
No insulation between primary and secondary 
for DC power supply
Dielectric strength2,300 VAC at 50/60 Hz for 1 min between 
the external AC and GR terminals, leakage 
current: 5 mA max.
No insulation between primary and secondary 
for DC power supply
Noise immunityConforms to IEC 61000-4-4. 2 kV (power supply line)
Vibration resistanceConforms to JIS C60068-2-6. 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, 
acceleration: 9.8 m/s2 in X, Y, and Z directions for 80 minutes each. Sweep time: 
8 minutes × 10 sweeps = total time of 80 minutes)
Shock resistanceConforms to JIS C60068-2-27. 147 m/s2 three times each in X, Y, and Z directions
Ambient operating 
temperature
0 to 55°C
Ambient humidity10% to 90% (with no condensation)
Ambient operating 
environment
No corrosive gas
Ambient storage 
temperature
-20 to 75°C (Excluding battery.)
Power holding time10 ms min.2 ms min.
Note: The above values are for a cold start at room temperature for an AC power supply, and for a cold start for a DC 
          power supply. 
          • A thermistor (with low-temperature current suppression characteristics) is used in the inrush current control 
              circuitry for the AC power supply. The thermistor will not be sufficiently cooled if the ambient temperature is 
              high or if a hot start is performed when the power supply has been OFF for only a short time. In those cases 
              the inrush current values may be higher (as much as two times higher) than those shown above. Always allow 
              for this when selecting fuses and breakers for external circuits. 
          • A capacitor charge-type delay circuit is used in the inrush current control circuitry for the DC power supply. The 
              capacitor will not be charged if a hot start is performed when the power supply has been OFF for only a short 
              time, so in those cases the inrush current values may be higher (as much as two times higher) than those 
              shown above.

Performance Specifications

TypeCP1H-XA 
CPU Units
CP1H-X 
CPU Units
CP1H-Y CPU Units
ModelsCP1H-XA[][][]-[]CP1H-X[][][]-[]CP1H-Y[][][]-[]
Control methodStored program method
I/O control methodCyclic scan with immediate refreshing
Program languageLadder diagram
Function blocksMaximum number of function block definitions: 128 Maximum number of instances: 256 
Languages usable in function block definitions: Ladder diagrams, structured text (ST)
Instruction length1 to 7 steps per instruction
InstructionsApprox. 500 (function codes: 3 digits)
Instruction execution timeBasic instructions: 0.10 μs min. Special instructions: 0.15 μs min.
Common processing time0.7 ms
Program capacity20K steps
Number of tasks288 (32 cyclic tasks and 256 interrupt tasks)
Scheduled 
interrupt tasks
1 (interrupt task No. 2, fixed)
Input interrupt 
tasks
8 (interrupt task No. 140 to 147, fixed)6 (interrupt task No. 140 to 145, fixed)
(Interrupt tasks can also be specified and executed for high-speed counter interrupts.)
Maximum subroutine 
number
256
Maximum jump number256
I/O areas 
*
Input bits272bits (17 words): CIO 0.00 to 16.15
Output bits272bits (17 words): CIO 100.00 to 116.16
Built-in Analog
Inputs
CIO 200 to CIO 203---
Built-in Analog
Outputs
CIO 210 to CIO 211---
Serial PLC 
Link Area
1,440 bits (90 words): CIO 3100.00 to CIO 3189.15 (CIO 3100 to CIO 3189)
Work bits8,192 bits (512 words): W0.00 to W511.15 (W0 to W511) 
CIO Area: 37,504 bits (2,344 words): CIO 3800.00 to CIO 6143.15 (CIO 3800 to CIO 6143)
TR Area16 bits: TR0 to TR15
Holding Area8,192 bits (512 words): H0.00 to H511.15 (H0 to H511)
AR AreaRead-only (Write-prohibited): 7168 bits (448 words): A0.00 to A447.15 (A0 to A447) 
Read/Write: 8192 bits (512 words): A448.00 to A959.15 (A448 to A959)
Timers4,096 bits: T0 to T4095
Counters4,096 bits: C0 to C4095
DM Area32 Kwords: D0 to D32767
Data Register Area16 registers (16 bits): DR0 to DR15
Index Register Area16 registers (32 bits): IR0 to IR15
Task Flag Area32 flags (32 bits): TK0000 to TK0031
Trace Memory4,000 words (500 samples for the trace data maximum of 31 bits and 6 words.)
Memory CassetteA special Memory Cassette (CP1W-ME05M) can be mounted. 
Note: Can be used for program backups and auto-booting.
Clock functionSupported. Accuracy (monthly deviation): 
-4.5 min to -0.5 min (ambient temperature: 55°C), 
-2.0 min to +2.0 min (ambient temperature: 25°C), 
-2.5 min to +1.5 min (ambient temperature: 0°C)
Communications functionsOne built-in peripheral port (USB 1.1): For connecting Support Software only.
A maximum of two Serial Communications Option Boards can be mounted.
A maximum of two Ethernet Option Boards can be mounted. When using CP1W-CIF41 
Ver.1.0, one Ethernet Option Board can be mounted.
Memory backupFlash memory: User programs, parameters (such as the PLC Setup), comment data, 
and the entire DM Area can be saved to flash memory as initial values. 
Battery backup: The Holding Area, DM Area, and counter values (flags, PV) are backed up
by a battery.
Battery service life5 years at 25°C. (Use the replacement battery within two years of manufacture.)
Built-in input terminals40 (24 inputs, 16 outputs)20 (12 inputs, 8 outputs) 
Line-driver inputs: Two axes for phases A, 
B, and Z 
Line-driver outputs: Two axes for CW and 
CCW
Number of connectable 
Expansion (I/O) Units
CP Expansion I/O Units: 7 max.; CJ-series Special I/O Units or CPU Bus Units: 2 max.
Max. number of I/O points320 (40 built in + 40 per Expansion (I/O) 
Unit × 7 Units)
300 (20 built in + 40 per Expansion (I/O) 
Unit × 7 Units)
Interrupt inputs8 inputs (Shared by the external interrupt 
inputs (counter mode) and the quick- 
response inputs.)
6 inputs (Shared by the external interrupt 
inputs (counter mode) and the quick- 
response inputs.)
Interrupt input counter 
mode
8 inputs (Response frequency: 5 kHz 
max. for all interrupt inputs), 16 bits 
Up or down counters
6 inputs (Response frequency: 5 kHz max. 
for all interrupt inputs), 16 bits 
Up or down counters
Quick-response inputs8 points (Min. input pulse width: 50 μs max.)6 points (Min. input pulse width: 50 μs max.)
Scheduled interrupts1
High-speed counters4 inputs: 
Differential phases (4x), 50 kHz or 
Single-phase (pulse plus direction, up/ 
down, increment), 100 kHz 
Value range: 32 bits, Linear mode or ring 
mode 
Interrupts: Target value comparison or 
range comparison
2 inputs: 
Differential phases (4x), 500 kHz or Single- 
phase, 1 MHz and 
2 inputs: 
Differential phases (4x), 50 kHz or Single- 
phase (pulse plus direction, up/down, 
increment), 100 kHz 
Value range: 32 bits, Linear mode or ring 
mode 
Interrupts: Target value comparison or 
range comparison
Pulse 
outputs 
(models 
with 
transistor
outputs 
only)
Pulse outputsTrapezoidal or S-curve acceleration and 
deceleration (Duty ratio: 50% fixed) 
4 outputs, 1 Hz to 100 kHz (CCW/CW or 
pulse plus direction)
Trapezoidal or S-curve acceleration and 
deceleration (Duty ratio: 50% fixed) 
2 outputs, 1 Hz to 1 MHz (CCW/CW or pulse 
plus direction) 
2 outputs, 1 Hz to 100 kHz (CCW/CW or 
pulse plus direction)
PWM outputsDuty ratio: 0.0% to 100.0% (Unit: 0.1%) 
2 outputs, 0.1 to 6553.5 Hz (Accuracy: ±5% at 1 kHz)
Built-in analog I/O terminals4 analog inputs and 
2 analog outputs
None
Analog control1 (Setting range: 0 to 255)
External analog input1 input (Resolution: 1/256, Input range: 0 to 10 V), not isolated
Note: The memory areas for CJ-series Special I/O Units and CPU Bus Units are allocated at the same as for the CJ-series. For details, refer to the CJ Series catalog (Cat. No. P052).

Tidak ada komentar: