CJ-series CompoBus/S Master Unit CJ1W-SRM21

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.
Unit 
type
NameSpecificationsNo. of 
unit 
numbers 
allocated
Current con- 
sumption (A)
ModelStand- 
ards
Communi- 
cations 
functions
No. of I/O 
points
Max. Units 
mountable 
per CPU 
Unit
5 V24 V
CJ1 
Special
I/O 
Units
CompoBus/S
Master Unit
Remote I/O 
communi- 
cations
256 max. 
(128 inputs 
and 
128 outputs)
401 or 2 
(variable)
0.15---CJ1W-SRM21UC1, 
N, L, 
CE,
128 max. 
(64 inputs 
and 
64 outputs)
Note: This unit cannot be used with the Machine Automation Controller NJ-series.

Communication Specifications

ItemSpecification
Communications methodSpecial CompoBus/S protocol
Communications baud rateHigh-speed Communications Mode: 750 kbps 
Long-distance Communications Mode: 93.75 kbps
Modulation methodBaseband method
Coding methodManchester coding method
Error control checksManchester code check, frame length check, and parity check
CableVCTF cable 
(JIS C 3306)
Two 0.75 mm2 conductors (2 signal wires) 
Four 0.75 mm2 conductors (2 signal wires and 2 power supply wires)
Special Flat 
Cable
Four 0.75 mm2 conductors (2 signal wires and 2 power supply wires)
Commu- 
nications 
distance
2-conductor 
VCTF cable
High-speed Communications Mode 
Main line length: 100 m max. 
Branch line length: 3 m max. 
Total branch line length: 50 m max.
Long-distance Communications Mode 
Main line length: 500 m max. 
Branch line length: 6 m max. 
Total branch line length: 120 m max.
4-conductor 
VCTF cable
High-speed Communications Mode 
Main line length: 30 m max. 
Branch line length: 3 m max. 
Total branch line length: 30 m max.
Long-distance Communications Mode: Flexibly branched, provided that the total length of 
cable is a maximum of 200 m.
Special Flat 
Cable
High-speed Communications Mode 
Main line length: 30 m max. 
Branch line length: 3 m max. 
Total branch line length: 30 m max. 
When 4-conductor VCTF cable or Special Flat Cable is used to connect fewer than 16 
Slaves, the main line can be up to 100 m long and the total branch line length can be up 
to 50 m in High-speed Communications Mode.
Long-distance Communications Mode: Flexibly branched, provided that the total length of 
cable is a maximum of 200 m.

Specifications

I/O points256 (128 inputs and 128 outputs) or 128 (64 inputs and 64 outputs) (Switch- 
selectable)
Applicable PLC modelsCJ-series PLCs
Unit typeSpecial I/O Unit
Allocated words *For 256 I/O: 20 words (8 for inputs, 8 for outputs, 4 for status) 
For 128 I/O: 10 words (4 for inputs, 4 for outputs, 2 for status)
No. of mountable Master Units40
Node address8 addresses per node
No. of connectable Slaves32
Status informationCommunications Error Flags, Participation Flags
* Uses Special I/O Unit Area (in CIO Area).