CJ-series EtherCAT® Slave Unit CJ1W-ECT21

International Standards

  • • The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives. 
    • Contact your OMRON representative for further details and applicable conditions for these standards.

EtherCAT Slave Unit

Unit type : CJ1 CPU Bus Unit
Product nameSpecificationsNo. of unit 
numbers
allocated
Current consumption (A)ModelStandards
Communications cableCommunications 
functions
5 V 
system
24 V 
system
EtherCAT 
Slave Unit 
 3439_lu_1_1
STP (shielded twisted-pair) 
cable of category 5 or higher 
with double shielding
Refreshing methods: 
Free-Run Mode 
PDO data sizes: 
TxPDO 400byte max./ 
RxPDO: 400byte max.
10.34--CJ1W-ECT21 *UC1, 
CE, 
KC
* When using with the Machine Automation Controller NJ /NXSeries, use CPU Units with unit version 1.10 or later and the Sysmac Studio version 1.13 or higher.

Recommended EtherCAT Communications Cables

Use Straight STP (shielded twisted-pair) cable of category 5 or higher with double shielding (braiding and aluminum foil tape) for EtherCAT.

Cable with Connectors

ItemAppearanceRecommended 
manufacturer
Cable 
length(m) *1
Model
Standard type 
Cable with Connectors on Both Ends 
(RJ45/RJ45) 
Wire Gauge and Number of Pairs: 
AWG27, 4-pair Cable 
Cable Sheath material: LSZH *2 
Cable color: Yellow *3
3439_lu_2_1OMRON0.3XS6W-6LSZH8SS30CM-Y
0.5XS6W-6LSZH8SS50CM-Y
1XS6W-6LSZH8SS100CM-Y
2XS6W-6LSZH8SS200CM-Y
3XS6W-6LSZH8SS300CM-Y
5XS6W-6LSZH8SS500CM-Y
Rugged type 
Cable with Connectors on Both Ends 
(RJ45/RJ45) 
Wire Gauge and Number of Pairs: 
AWG22, 2-pair Cable
3439_lu_2_2OMRON0.3XS5W-T421-AMD-K
0.5XS5W-T421-BMD-K
1XS5W-T421-CMD-K
2XS5W-T421-DMD-K
5XS5W-T421-GMD-K
10XS5W-T421-JMD-K
Rugged type 
Cable with Connectors on Both Ends 
(M12 Straight/RJ45) 
Wire Gauge and Number of Pairs: 
AWG22, 2-pair Cable
3439_lu_2_3OMRON0.3XS5W-T421-AMC-K
0.5XS5W-T421-BMC-K
1XS5W-T421-CMC-K
2XS5W-T421-DMC-K
5XS5W-T421-GMC-K
10XS5W-T421-JMC-K
Rugged type 
Cable with Connectors on Both Ends 
(M12 Right-angle/RJ45) 
Wire Gauge and Number of Pairs: 
AWG22, 2-pair Cable
3439_lu_2_4OMRON0.3XS5W-T422-AMC-K
0.5XS5W-T422-BMC-K
1XS5W-T422-CMC-K
2XS5W-T422-DMC-K
5XS5W-T422-GMC-K
10XS5W-T422-JMC-K
*1. Standard type cables length 0.2, 0.3, 0.5, 1, 1.5, 2, 3, 5, 7.5, 10, 15 and 20m are available. Rugged type cables length 0.3, 0.5, 1, 2, 3, 5, 10 and 15m are available. 
*2. The lineup features Low Smoke Zero Halogen cables for in-cabinet use and PUR cables for out-of-cabinet use. 
*3. Cables colors are available in blue, yellow, or Green 
Note: For details, refer to Cat.No.G019.

Cable / Connectors

Wire Gauge and Number of Pairs: AWG24, 4-pair Cable

ItemAppearanceRecommended manufacturerModel
Cables----Hitachi Metals, Ltd.NETSTAR-C5E SAB 0.5 × 4P*
----Kuramo Electric Co.KETH-SB*
---SWCC Showa Cable Systems Co.FAE-5004*
RJ45 Connectors----Panduit CorporationMPS588-C*
* We recommend you to use above cable and connector together.

Wire Gauge and Number of Pairs: AWG22, 2-pair Cable

ItemAppearanceRecommended manufacturerModel
Cables----Kuramo Electric Co.KETH-PSB-OMR*
---JMACS Japan Co., Ltd.PNET/B*
RJ45 Assembly Connector3439_lu_4_1OMRONXS6G-T421-1*
* We recommend you to use above cable and connector together. 
Note: Connect both ends of cable shielded wires to the connector hoods.


General Specification

The general specifications conform to those of the CJ-series PLCs, CP-series PLCs and NSJ-series PLCs.

Specifications

EtherCAT Slave Unit CJ1W-ECT21

ItemSpecification
Model numberCJ1W-ECT21
Applicable PLCsNJ-series, CJ-series, CP-series, NSJ-series
Unit classificationCPU Bus Unit
Applicable unit numbers0 to F
Mounting positionCPU Rack or Expansion Rack
Number of Units that can be mounted16 Units max. (you must allocate unique words)
CPU Unit 
words used
Allocated CIO Area words 
(CPU Bus Unit words) *1
25 words/Unit (one unit number’s words)
Unit Status 1, Unit Status 2, Slave Status 1, Slave Status 2
Allocated DM Area words 
(CPU Bus Unit words) *2
100 words/Unit (one unit number’s words)
I/O Communication Area Setting Table, I/O Communication Area Reference Table
Other I/O memory *3I/O communication area in any area *4
CPU Bus Unit setting areaNot used
Transmission
specifications
Communications protocolEtherCAT protocol
ModulationBaseband
Baud rate100 Mbps
Physical layer100BASE-TX (IEEE 802.3)
TopologyDepends on the specifications of the EtherCAT master
Transmission mediaCategory 5 or higher twisted-pair cable (Recommended cable: double-shielded cable with aluminum tape and braiding)
Transmission distanceDistance between nodes: 100 m or less
Send/receive PDO data sizesAllocatable IN and OUT data area sizes of 0, 50, 100, 200 or 400 bytes
Mailbox data sizeInput: 512 bytes 
Output: 512 bytes
MailboxEmergency messages and SDO requests
Refreshing methodsFree-Run Mode
Node address setting range1 to 255 (hardware switch setting) 
1 to 65535 (software switch setting)
Current consumption340 mA max. at 5 V DC
Weight97 g max.
Dimensions31 × 90 × 65 mm (W × H × D)
*1. Access via the device variables for CJ-series Unit when using NJ-serires CPU Units. 
*2. Using the user-defined variable for R/W to the allocation area when using NJ-serires CPU Units. 
*3. The IN and OUT data exchanged with the EtherCAT master is designated to memory areas by configuring the I/O Communication Area Setting Table. Refer to “CJ-series EtherCAT Slave Units Operation Manual” for NJ-series CPU Unit (W542) 
*4. Set with allocated DM area words (CPU Bus Unit words) or CX-Programmer when using CJ/CP/NSJ-series CPU Units.

EtherCAT Communications Specifications

ItemSpecification
Communications standardIEC 61158 Type 12
Physical layer100BASE-TX (IEEE 802.3)
ModulationBaseband
Baud rate100 Mbps
TopologyDepends on the specifications of the EtherCAT master.
Transmission mediaCategory 5 or higher twisted-pair cable (Recommended cable: double-shielded cable with aluminum tape and braiding)
Transmission distanceDistance between nodes: 100 m or less

Unit Versions and Software Versions

Model mumber of 
EtherCAT Slave Unit
Unit 
version
Corresponding unit version/version *
Using NJ CPU UnitUsing CJ/CP/NSJ-series CPU Unit
Unit version of 
CPU Units
Sysmac Studio VersionUnit version of 
CPU Units
CX-Programmer version
CJ1W-ECT21Ver.1.0Ver.1.10 or laterVer.1.13 or higherThe oldest available 
version or later
Ver.9.54 or higher
* Some Units do not have all of the versions given in the above table. If a Unit does not have the specified version, support is provided by the oldest available version after the specified version. Refer to the user’fs manuals for the specific Units for the relation between models and versions.