International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.

Basic Model

Renewal-type

E[][]S-type CP1E CPU Units (Built-in USB port)

Product 
name
SpecificationsEx- 
ternal 
power 
supply 
(24 
VDC) 
(A)
Current 
consump- 
tion (A)
ModelStand- 
ards
Power 
Supply
In- 
puts
Out- 
puts
Out- 
put 
type
Pro- 
gram 
ca- 
pacity
Data 
memory 
capacity
5 V24 V
E[][]S-type 
CPU Units 
with 14 I/O 
Points
2064_lu_1_1
100 to 
240 
VAC
86Relay2K 
steps
2K words--0.160.07CP1E-E14SDR-ACE
E[][]S-type 
CPU Units 
with 20 I/O 
Points
2064_lu_1_2
100 to 
240 
VAC
128Relay2K 
steps
2K words--0.170.08CP1E-E20SDR-ACE
E[][]S-type 
CPU Units 
with 30 I/O 
Points
2064_lu_1_3
100 to 
240 
VAC
1812Relay2K 
steps
2K words0.30.170.07CP1E-E30SDR-ACE
E[][]S-type 
CPU Units 
with 40 I/O 
Points
2064_lu_1_4
100 to 
240 
VAC
2416Relay2K 
steps
2K words0.30.170.09CP1E-E40SDR-ACE
E[][]S-type 
CPU Units 
with 60 I/O 
Points
2064_lu_1_5
100 to 
240 
VAC
3624Relay2K 
steps
2K words0.30.170.13CP1E-E60SDR-ACE

Normal-type

E[][]-type CP1E CPU Units (Built-in USB port)

Product 
name
SpecificationsEx- 
ternal 
power 
supply 
(24 
VDC) 
(A)
Current 
consump- 
tion (A)
ModelStand- 
ards
Power 
Supply
In- 
puts
Out- 
puts
Output 
type
Pro- 
gram 
ca- 
pacity
Data 
mem- 
ory 
ca- 
pacity
5 V24 V
E[][]-type 
CPU Units 
with 10 
I/O Points
2064_lu_5_1
100 to 
240 
VAC
64Relay2K 
steps
2K 
words
---0.080.04CP1E-E10DR-AUC1, 
N, L, 
CE
Transistor 
(sinking)
---0.11---CP1E-E10DT-A
Transistor 
(sourcing)
---0.11---CP1E-E10DT1-A
24 VDCRelay---0.080.04CP1E-E10DR-D
Transistor 
(sinking)
---0.11---CP1E-E10DT-D
Transistor 
(sourcing)
---0.11---CP1E-E10DT1-D
E[][]-type 
CPU Units 
with 14 
I/O Points
2064_lu_5_2
100 to 
240 
VAC
86Relay2K 
steps
2K 
words
---0.160.07CP1E-E14DR-AUC1, 
N, L, 
CE
E[][]-type 
CPU Units 
with 20 
I/O Points
2064_lu_5_3
100 to 
240 
VAC
128Relay2K 
steps
2K 
words
---0.170.08CP1E-E20DR-AUC1, 
N, L, 
CE
E[][]-type 
CPU Units 
with 30 
I/O Points
2064_lu_5_4
100 to 
240 
VAC
1812Relay2K 
steps
2K 
words
0.30.170.07CP1E-E30DR-AUC1, 
N, L, 
CE
E[][]-type 
CPU Units 
with 40 
I/O Points
2064_lu_5_5
100 to 
240 
VAC
2416Relay2K 
steps
2K 
words
0.30.170.09CP1E-E40DR-AUC1, 
N, L, 
CE

Application Model

Renewal-type

N[][]S1-type CP1E CPU Units (Built-in RS-232C, RS-485, USB ports)

Product 
name
SpecificationsEx- 
ternal 
power 
supply 
(24 
VDC) 
(A)
Current 
consump- 
tion (A)
ModelStand- 
ards
Power 
Supply
In- 
puts
Out- 
puts
Output 
type
Pro- 
gram 
ca- 
pacity
Data 
mem- 
ory 
ca- 
pacity
5 V24 V
N[][]S1- 
type CPU 
Units 
with 30 
I/O Points
2064_lu_2_1
100 to 
240 
VAC
1812Relay8K 
steps
8K 
words
0.30.210.07CP1E-N30S1DR-ACE
DC24VTransistor 
(sinking)
--0.270.02CP1E-N30S1DT-D
Transistor 
(sourcing)
--0.270.02CP1E-N30S1DT1-D
N[][]S1- 
type CPU 
Units 
with 40 
I/O Points
2064_lu_2_2
100 to 
240 
VAC
2416Relay8K 
steps
8K 
words
0.30.210.09CP1E-N40S1DR-ACE
DC24VTransistor 
(sinking)
--0.310.02CP1E-N40S1DT-D
Transistor 
(sourcing)
--0.310.02CP1E-N40S1DT1-D
N[][]S1- 
type CPU 
Units 
with 60 
I/O Points
2064_lu_2_3
100 to 
240 
VAC
3624Relay8K 
steps
8K 
words
0.30.210.13CP1E-N60S1DR-ACE
DC24VTransistor 
(sinking)
--0.310.02CP1E-N60S1DT-D
Transistor 
(sourcing)
--0.310.02CP1E-N60S1DT1-D

N[][]S-type CP1E CPU Units (Built-in RS-232C, USB ports)

Product 
name
SpecificationsEx- 
ternal 
power 
supply 
(24 
VDC) 
(A)
Current 
consump- 
tion (A)
ModelStand- 
ards
Power 
Supply
In- 
puts
Out- 
puts
Output 
type
Pro- 
gram 
ca- 
pacity
Data 
mem- 
ory 
ca- 
pacity
5 V24 V
N[][]S- 
type CPU 
Units 
with 30 
I/O Points
2064_lu_3_1
100 to 
240 
VAC
1812Relay8K 
steps
8K 
words
0.30.210.07CP1E-N30SDR-ACE
DC24VTransistor 
(sinking)
--0.270.02CP1E-N30SDT-D
Transistor 
(sourcing)
--0.270.02CP1E-N30SDT1-D
N[][]S- 
type CPU 
Units 
with 40 
I/O Points
2064_lu_3_2
100 to 
240 
VAC
2416Relay8K 
steps
8K 
words
0.30.210.09CP1E-N40SDR-ACE
DC24VTransistor 
(sinking)
--0.310.02CP1E-N40SDT-D
Transistor 
(sourcing)
--0.310.02CP1E-N40SDT1-D
N[][]S- 
type CPU 
Units 
with 60 
I/O Points
2064_lu_3_3
100 to 
240 
VAC
3624Relay8K 
steps
8K 
words
0.30.210.13CP1E-N60SDR-ACE
DC24VTransistor 
(sinking)
--0.310.02CP1E-N60SDT-D
Transistor 
(sourcing)
--0.310.02CP1E-N60SDT1-D

Normal-type

N/NA[][]-type CP1E CPU Units (Built-in RS-232C, USB ports)

Product 
name
SpecificationsEx- 
ternal 
power 
supply 
(24 
VDC) 
(A)
Current 
consump- 
tion (A)
ModelStand- 
ards
Pow- 
er 
Sup- 
ply
In- 
puts
Out- 
puts
Output 
type
Pro- 
gram 
ca- 
pacity
Data 
mem- 
ory 
ca- 
pacity
5 V24 V
N[][]-type 
CPU Units 
with 14 
I/O Points
2064_lu_6_1
100 
to 
240 
VAC
86Relay8K 
steps
8K 
words
---0.170.07CP1E-N14DR-AUC1, 
N, L, 
CE
Transistor 
(sinking)
---0.220.02CP1E-N14DT-A
Transistor 
(sourcing)
---0.220.02CP1E-N14DT1-A
24 
VDC
Relay---0.170.07CP1E-N14DR-D
Transistor 
(sinking)
---0.220.02CP1E-N14DT-D
Transistor 
(sourcing)
---0.220.02CP1E-N14DT1-D
N[][]-type 
CPU Units 
with 20 
I/O Points
2064_lu_6_2
100 
to 
240 
VAC
128Relay8K 
steps
8K 
words
---0.180.08CP1E-N20DR-AUC1, 
N, L, 
CE
Transistor 
(sinking)
---0.230.02CP1E-N20DT-A
Transistor 
(sourcing)
---0.230.02CP1E-N20DT1-A
24 
VDC
Relay---0.180.08CP1E-N20DR-D
Transistor 
(sinking)
---0.230.02CP1E-N20DT-D
Transistor 
(sourcing)
---0.230.02CP1E-N20DT1-D
N[][]-type 
CPU Units 
with 30 
I/O Points
2064_lu_6_3
100 
to 
240 
VAC
1812Relay8K 
steps
8K 
words
0.30.210.07CP1E-N30DR-AUC1, 
N, L, 
CE
Transistor 
(sinking)
0.30.270.02CP1E-N30DT-A
Transistor 
(sourcing)
0.30.270.02CP1E-N30DT1-A
24 
VDC
Relay---0.210.07CP1E-N30DR-D
Transistor 
(sinking)
---0.270.02CP1E-N30DT-D
Transistor 
(sourcing)
---0.270.02CP1E-N30DT1-D
N[][]-type 
CPU Units 
with 40 
I/O Points
2064_lu_6_4
100 
to 
240 
VAC
2416Relay8K 
steps
8K 
words
0.30.210.09CP1E-N40DR-AUC1, 
N, L, 
CE
Transistor 
(sinking)
0.30.310.02CP1E-N40DT-A
Transistor 
(sourcing)
0.30.310.02CP1E-N40DT1-A
24 
VDC
Relay---0.210.09CP1E-N40DR-D
Transistor 
(sinking)
---0.310.02CP1E-N40DT-D
Transistor 
(sourcing)
---0.310.02CP1E-N40DT1-D
N[][]-type 
CPU Units 
with 60 
I/O Points
2064_lu_6_5
100 
to 
240 
VAC
3624Relay8K 
steps
8K 
words
0.30.210.13CP1E-N60DR-AUC1, 
N, L, 
CE
Transistor 
(sinking)
0.30.310.02CP1E-N60DT-A
Transistor 
(sourcing)
0.30.310.02CP1E-N60DT1-A
24 
VDC
Relay---0.210.13CP1E-N60DR-D
Transistor 
(sinking)
---0.310.02CP1E-N60DT-D
Transistor 
(sourcing)
---0.310.02CP1E-N60DT1-D
NA-type 
CPU Units 
with 20 
I/O Points 
(Built-in 
analog)
2064_lu_6_6
100 
to 
240 
VAC
12 
(Built- 
in 
ana- 
log 
in- 
puts: 
2)

(Built- 
in 
ana- 
log 
out- 
puts: 
1)
Relay8K 
steps
8K 
words
0.30.180.11CP1E-NA20DR-AUC1, 
N, L, 
CE
24 
VDC
Transistor 
(sinking)
---0.230.09CP1E-NA20DT-D
Transistor 
(sourcing)
---0.230.09CP1E-NA20DT1-D

Optional Products

Battery Set

Product 
name
SpecificationsModelStand- 
ards
Battery Set
2064_lu_7_1
For N/NA[][](S[])-type CP1E CPU Units 
Note: Mount a Battery to an N/NA[][](S[])-type CPU Unit if the data in the 
following areas must be backed up for power interruptions. 
DM Area (D) (except backed up words in the DM Area), Holding Area (H), 
Counter Completion Flags (C), Counter Present Values (C), Auxiliary Area (A), 
and Clock Function 
(Use batteries within two years of manufacture.)
CP1W-BAT01--

Option Board (for CP1E N30/40/60 or NA20 CPU Units)

The Options cannot be used for CP1E N14/20, N30/40/60S(1), E10/14/20/30/40/60(S) CPU Units.
Product nameSpecificationsModelStand- 
ards
RS-232C 
Option Board
2064_lu_8_1One RS-232C Option Board can be mounted to the 
Option Board slot. 
One RS-232C connector is included.
CP1W-CIF01UC1, 
N, L, 
CE
RS-422A/485 
Option Board
2064_lu_8_2One RS-422A/485 Option Board can be mounted to the 
Option Board slot.
CP1W-CIF11
RS-422A/485 
Isolated-type 
Option Board
2064_lu_8_3CP1W-CIF12
Ethernet 
Option Board
2064_lu_8_4One Ethernet Option Board can be mounted to the 
Option Board slot. 
CP1E CPU Units are supported by CP1W-CIF41 
version 2.0 or higher. 
When using CP1W-CIF41, CX-Programmer version 
9.12 or higher is required.
CP1W-CIF41
Analog Input 
Option Board
2064_lu_8_5Can be mounted in CPU Unit Option Board slot. 
2 analog inputs. 0-10V(Resolution:1/4000), 0-20mA 
(Resolution:1/2000).
CP1W-ADB21 *
Analog Output 
Option Board
2064_lu_8_6Can be mounted in CPU Unit Option Board slot. 
2 analog outputs. 0-10V (Resolution:1/4000).
CP1W-DAB21V *
Analog I/O 
Option Board
2064_lu_8_7Can be mounted in CPU Unit Option Board slot. 
2 analog inputs. 0-10V(Resolution:1/4000), 0-20mA 
(Resolution:1/2000). 
2 analog outputs. 0-10V (Resolution:1/4000).
CP1W-MAB221 *
Note: It is not possible to use a CP-series Ethernet Option Board version 1.0 (CP1W-CIF41), LCD Option Board (CP1W- 
          DAM01), or Memory Card (CP1W-ME05M) with a CP1E CPU Unit. 
* Support is provided with CP1E CPU Unit version 1.2 and later.

Expansion I/O Units and Expansion Units (for CP1E E30/40/60(S), N30/40/60(S[]), or NA20 CPU Units)

CP1E E10/14/20(S) or N14/20 CPU Units do not support Expansion I/O Units and Expansion Units.
Unit 
type
Product 
name
SpecificationsCurrent 
consump- 
tion (A)
ModelStand- 
ards
In- 
puts
Out- 
puts
Output type5 V24 V
CP1W 
Expan- 
sion 
I/O 
Units
Input Unit 
2064_lu_11_1
8---24 VDC Input0.018--CP1W-8EDU, C, 
N, L, 
CE
Output Units 
2064_lu_11_2
---8Relay0.0260.044CP1W-8ER
Transistor (sinking)0.075--CP1W-8ET
Transistor (sourcing)0.075--CP1W-8ET1
Output Units 
2064_lu_11_3
---16Relay0.0420.090CP1W-16ERN, L, 
CE
Transistor (sinking)0.076--CP1W-16ET
Transistor (sourcing)0.076--CP1W-16ET1
Output Units 
2064_lu_11_4
---32Relay0.0490.131CP1W-32ERN, L, 
CE
Transistor (sinking)0.113--CP1W-32ET
Transistor (sourcing)0.113--CP1W-32ET1
I/O Units 
2064_lu_11_5
128Relay0.1030.044CP1W-20EDR1U, C, 
N, L, 
CE
Transistor (sinking)0.130--CP1W-20EDT
Transistor (sourcing)0.130--CP1W-20EDT1
I/O Units 
2064_lu_11_6
2416Relay0.0800.090CP1W-40EDRN, L, 
CE
Transistor (sinking)0.160--CP1W-40EDT
Transistor (sourcing)0.160--CP1W-40EDT1
CP1W 
Expan- 
sion 
Units
Analog 
Input Unit 
2064_lu_11_7
4CH--Input range: 
0 to 5 V, 1 to 5 V, 
0 to 10 V, ±10 V, 
0 to 20 mA, 
or 4 to 20 mA.
Resolution: 
1/6000
0.1000.090CP1W-AD041UC1, 
N, L, 
CE
Resolution: 
1/12000
0.1000.050CP1W-AD042UC1, 
N, CE
Analog 
Output Unit 
2064_lu_11_8
--2CHOutput range: 
1 to 5 V, 0 to 
10 V, ±10 V, 
0 to 20 mA, 
or 4 to 20 mA.
Resolution: 
1/6000
0.0400.095CP1W-DA021UC1, 
N, L, 
CE
--4CHResolution: 
1/6000
0.0800.124CP1W-DA041
Resolution: 
1/12000
0.0700.160CP1W-DA042UC1, 
N, CE
Analog 
I/O Unit 
2064_lu_11_9
4CH4CHInput range: 
0 to 5 V, 1 to 5 V, 
0 to 10 V, ±10 V, 
0 to 20 mA, or 
4 to 20 mA. 
Output range: 
1 to 5 V, 0 to 10 V, 
±10 V, 0 to 20 mA, 
or 4 to 20 mA.
Resolution: 
1/12000
0.1200.170CP1W-MAD44UC1, 
N, CE
4CH2CHResolution: 
1/12000
0.1200.120CP1W-MAD42
2CH1CHResolution: 
1/6000
0.0830.110CP1W-MAD11UC1, 
N, L, 
CE
Temperature 
Sensor Unit 
2064_lu_11_10
2CH--Sensor type: Thermocouple 
(J or K)
0.0400.059CP1W-TS001UC1, 
N, L, 
CE
4CH--Sensor type: Thermocouple 
(J or K)
0.0400.059CP1W-TS002
2CH--Sensor type: Platinum resistance 
thermometer (Pt100 or JPt100)
0.0540.073CP1W-TS101
4CH--Sensor type: Platinum resistance 
thermometer (Pt100 or JPt100)
0.0540.073CP1W-TS102
4CH--Sensor type: 
Thermocouple 
(J or K) 
2channels can be 
used as analog input. 
Input range: 
1 to 5 V, 0 to 10 V, 
4-20 mA
Resolution: 
1/12000
0.0700.030CP1W-TS003UC1, 
N, CE
12CH--Sensor type: Thermocouple 
(J or K)
0.0800.050CP1W-TS004
CompoBus/S 
I/O Link Unit 
2064_lu_11_11
88CompoBus/S slave0.029--CP1W-SRT21UC1, 
N, L, 
CE

I/O Connecting Cable

Product nameSpecificationsModelStandards
I/O Connecting Cable80 cm (for CP1W Expansion I/O Units and Expansion Units) 
Only one I/O Connecting Cable can be used in each PLC.
CP1W-CN811UC1, N, 
L, CE
Note: An I/O Connecting Cable (approx. 6 cm) for horizontal connection is provided with CP1W Expansion I/O Units and 
          Expansion Units.

DIN Track Accessories

NameSpecificationsModelStandards
DIN TrackLength: 0.5 m; Height: 7.3 mmPFP-50N--
Length: 1 m; Height: 7.3 mmPFP-100N
Length: 1 m; Height: 16 mmPFP-100N2
End PlateA stopper to secure the Units on the DIN Track.PFP-M

Programming Devices

Software

Product 
name
SpecificationsModelStand- 
ards
Number 
of 
licenses
Media
FA Integrated 
Tool Package 
CX-One Lite 
Ver.4.[]
CX-One Lite is a subset of the complete CX-One 
package that provides only the Support Software 
required for micro PLC applications. 
CX-One Lite runs on the following OS. 
OS: Windows XP (Service Pack 3 or higher, 32-bit 
version)/Windows Vista (32-bit/64-bit version)/ 
Windows 7 (32-bit/64-bit version)/Windows 8 (32- 
bit/64-bit version)/Windows 8.1 (32-bit/64-bit 
version) 
CX-One Lite Ver. 4.[] includes Micro PLC Edition 
CX-Programmer Ver.9.[].
1 licenseCDCXONE-LT01C-V4---
FA Integrated 
Tool Package 
CX-One 
Package 
Ver. 4.[]
CX-One is a comprehensive software package that 
integrates Support Software for OMRON PLCs and 
components. CX-One runs on the following OS. 
OS: Windows XP (Service Pack 3 or higher, 32-bit 
version)/Windows Vista (32-bit/64-bit version)/ 
Windows 7 (32-bit/64-bit version)/Windows 8 (32- 
bit/64-bit version)/Windows 8.1 (32-bit/64-bit 
version) 
CX-One Ver. 4.[] includes CX-Programmer Ver. 9.[].
1 license 
*
DVDCXONE-AL01D-V4---
Note: 1. The E20/30/40(S), N20/N30/N40(S) CPU Units are supported by CX-Programmer version 8.2 or higher. 
              The E10, E14, N14, N60, and NA20 CPU Units are supported by CX-Programmer version 9.03 or higher. When 
              Micro PLC Edition CXProgrammer is used, you need version 9.03 or higher. 
              The E60S CPU Units are supported by CX-Programmer version 9.42 or higher. When Micro PLC Edition CX- 
              Programmer is used, you need version 9.42 or higher. 
           2. The CX-One and CX-One Lite cannot be simultaneously installed on the same computer. 
* Multi licenses are available for the CX-One (3, 10, 30 or 50 licenses).
The following tables lists the Support Software that can be installed from CX-One
Support Software in CX-OneCX-One Lite Ver.4.[]CX-One Ver.4.[]
Micro PLC Edition CX-ProgrammerVer.9.[]YesNo
CX-ProgrammerVer.9.[]NoYes
CX-IntegratorVer.2.[]YesYes
Switch Box UtilityVer.1.[]YesYes
CX-ProtocolVer.1.[]NoYes
CX-SimulatorVer.1.[]YesYes
CX-PositionVer.2.[]NoYes
CX-Motion-NCFVer.1.[]NoYes
CX-Motion-MCHVer.2.[]NoYes
CX-MotionVer.2.[]NoYes
CX-DriveVer.1.[]YesYes
CX-Process ToolVer.5.[]NoYes
Faceplate Auto-Builder for NSVer.3.[]NoYes
CX-DesignerVer.3.[]YesYes
NV-DesignerVer.1.[]YesYes
CX-ThermoVer.4.[]YesYes
CX-ConfiguratorFDTVer.1.[]YesYes
CX-FLnetVer.1.[]NoYes
Network ConfiguratorVer.3.[]YesYes
CX-ServerVer.4.[]YesYes