Jual PLC Omron, PLC Mitsubishi, Inverter Omron, HMI Omron, HMI Weintek

PLC , HMI , INVERTER & SERVO : OMRON , MITSUBISHI , WEINTEK / WEINVIEW , DELTA , LS/LG , INVERTER DANFOSS , PRO-FACE , EMERSON , SHIHLIN ELECTRIC , SLANVERT , etc

Gedung LTC-Glodok Lantai 1 Blok B25 No.5 JAKARTA

Alamat Perwakilan Glodok: Gedung LTC-Glodok Lantai 1 Blok B25 No.5 , JAKARTA

Rabu, 25 Mei 2016

CJ-series CompoNet Master Units CJ1W-CRM21

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL(Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.
NameAppear- 
ance
SpecificationsNumber 
of unit 
numbers 
allocated
Power 
consumption (A)
ModelStand- 
ards
Type of 
communi- 
cations
Maximum number 
of I/O points per 
Master Unit
5-V 
system
24-V 
system
CJ1 
Special 
I/O Unit
1779_lu_1_1Remote I/O 
communica- 
tions 
Message 
communica- 
tions
Word Slave Units: 
1,024 inputs and 1,024 
outputs (2,048 I/O 
points total) 
Bit Slave Units: 256 
inputs and 256 outputs 
(512 I/O points total)
1, 2, 4, 
or 8
0.4-CJ1W-CRM21CE, U, 
U1, L, 
N
Note: Observe the following precautions if you use the CompoNet Master Unit in an NJ-series Machine Automation 
          Controller. 
           • Supported only by the CPU Units with unit version 1.01 or later and the Sysmac Studio version 1.02 or higher. 
           • You cannot use the simple backup function. 
           • You cannot send FINS commands to the CompoNet Master Unit.

Software

How to Select Required Support Software for Your Controller

The required Support Software depends on the Controller to connect. Please check the following table when purchasing the Support Software.
ItemOmron PLC SystemOmron Machine Automation Controller System
ControllerCS,CJ,CP,and other seriesNJ-series
SoftwareFA Integrated Tool Package CX-OneAutomation Software Sysmac Studio

FA Integrated Tool Package CX-One

Product 
name
SpecificationsModelStand- 
ards
Number of 
licenses
Media
FA 
Integrated 
Tool 
Package 
CX-One 
Ver.4.[]
The CX-One is a comprehensive software package 
that integrates Support Software for OMRON PLCs 
and components. 

CX-One runs on the following OS. 
OS:Windows XP (Service Pack 3 or higher, 32-bit 
version)/Windows Vista (32-bit/64-bit version)/ 
Windows 7 (32-bit/64-bit version)/Windows 8 (32-bit/ 
64-bit version)/Windows 8.1 (32-bit/64-bit version) / 
Windows 10 (32-bit/64-bit version) 

CX-One Version 4.[] includes CX-Integrator Ver.3.[]. 
For details, refer to the CX-One catalog (Cat. No. 
R134)
1 license 
*
DVDCXONE-AL01D-V4-
* Multi licenses (3, 10, 30, or 50 licenses) and DVD media without licenses are also available for the CX-One.

Automation Software Sysmac Studio

Please purchase a DVD and required number of licenses the first time you purchase the Sysmac Studio. DVDs and licenses are available individually. Each model of licenses does not include any DVD.
Product 
name
SpecificationsModelStand- 
ards
Number of 
licenses
Media
Sysmac 
Studio 
Standard
Edition 
Ver.1.[][]
The Sysmac Studio provides an integrated development 
environment to set up, program, debug, and maintain 
NJ-series Controllers and other Machine Automation 
Controllers, as well as EtherCAT slaves. 

Sysmac Studio runs on the following OS. 
OS: 
Windows XP (Service Pack 3 or higher, 32-bitversion) / 
Windows Vista (32-bit version) / 
Windows 7 (32-bit/64-bit version) / 
Windows 8 (32-bit/64-bit version) / 
Windows 8.1 (32-bit/64-bitversion) / 
Windows 10 (32-bit/64-bit version) 

The Sysmac Studio Standard Edition DVD includes 
Support Software to set up EtherNet/IP Units, DeviceNet
slaves, Serial Communications Units, and Support 
Software for creating screens on HMIs (CX-Designer). 
For details, refer to the Sysmac Integrated Catalogue 
(P072).

(Media only)
DVDSYSMAC-SE200D-
1 license 
*
-SYSMAC-SE201L-
* Multi licenses are available for the Sysmac Studio (3, 10, 30, or 50 licenses).

Communication Specifications

ItemSpecification
Communications protocolCompoNet Network protocol
Types of communicationsRemote I/O communications (programless,constant sharing of data with Slave Units)and message 
communications (explicit message communications as required with Slave Units and FINS message 
communications as required with Controllers *1)
Baud rate4 Mbps *2,3 Mbps,1.5 Mbps,93.75 kbps
ModulationBase-band
CodingManchester code
Error controlManchester code rules,CRC
Communications mediaThe following media can be used.*
Round cable I (JIS C 3306,2-conductor 0.75 mm2) 
Round cable II (JIS C3306 4-conductor 0.75 mm2) 
Flat Cable I (DCA4-4F10 Standard Flat Cable) 
Flat Cable II (DCA5-4F10 Sheathed Flat Cable)
Communications distance 
and wiring
Refer to Cable Types,Baud Rates,and Maximum Distances.
Connectable Master UnitsCompoNet Master Units
Connectable Slave UnitsCompoNet Slave Units
Maximum I/O capacityWord Slave Units:1,024 inputs and 1,024 outputs (2,048 I/O points total) 
Bit Slave Units:256 inputs and 256 outputs (512 I/O points total)
Maximum number of nodesWord Slave Units:64 input nodes and 64 output nodes 
Bit Slave Units:128 input nodes and 128 output nodes 
Repeater Units:64 nodes
Bits allocated per node 
address
Word Slave Units:16 bits 
Bit Slave Units:2 bits
Maximum number of nodes 
per trunk line or sub-trunk 
line
32 nodes (including Repeater Units)
Applicable node addressesWord Slave Units:IN0 to IN63 and OUT0 to OUT63 
Bit Slave Units:IN0 to IN127 and OUT0 to OUT127 
Repeater Units:0 to 63
Repeater Unit application 
conditions
Up to 64 Repeater Units can be connected per network.When Repeater Units are connected in series 
from the Master Unit,up to 2 extra segment layers can be created (i.e.,up to 2 Repeater Units are 
allowed between a Slave Unit and the Master Unit).
Signal linesTwo lines:BDH (communications data high)and BDL (communications data low)
Power linesTwo lines:BS+and BS -(power for communications and internal Slave Unit circuits) 
Power is supplied from the Master Unit or Repeater Units.
Communications power 
supply
24 VDC ± 10%
Connection formsFlat Cable at baud rate of 93.75 kbps:No restrictions 
Other cables or baud rates:Trunk line and branch lines
Connections for Slave Units and Repeater Units:T-branch or multidrop connections
*1. FINS message communications are supported by CJ-series Controllers only. 
*2. Drop-line connections are not supported with a baud rate of 4 Mbps, so Slaves with prewired cables (Bit Slaves) 
       cannot be used. 
*3. Round cable, Flat Cable, and Flat Cable II are all different types of cable. To use more than one type of cable at a 
        time, Repeater Units must be used to separate them on trunk lines and sub-trunk lines.

Cable Types, Baud Rates, and Maximum Distances

This section provides specifications on the maximum cable length and maximum number of nodes for each type of cable. Do not exceed these specifications.
CJ1W-CRM21 Specifications 3

Restrictions (at Baud Rate of 4 Mbps (No Branch Lines))

Cable typeMaximum length per segment 
(maximum length with 
Repeater Units)
Branch
line 
length
Total branch 
line length 
per segment
Branch 
location 
restrictions
Maximum number of 
Slave Units per 
segment *2
Round cable I30 m (90 m)0 m *10 m *1-32 nodes
Flat Cable I and Flat Cable II 
Round Cable II
30 m (90 m)0 m *10 m *1-32 nodes
*1. T-branches cannot be connected (only multidrop connections are possible). 
*2. Number of nodes including Repeater Units

Restrictions (at Baud Rate of 3 Mbps)

Cable typeMaximum length 
per segment 
(maximum 
length with 
Repeater Units)
Branch
line 
length
Total 
branch line 
length per 
segment
Branch 
location 
restrictions
Maximum
number of 
nodes per 
branch *1
Sub- 
branch
line 
length
Total sub- 
branch line 
length per 
segment
Maximum 
number 
of Slave 
Units per 
segment *2
Round cable I30 m (90 m)0.5 m8 m3 branches/m1 node0 m0 m32 nodes
Flat Cable I 
and Flat Cable II 
Round Cable II
30 m (90 m)0.5 m8 m3 branches/m1 node0 m0 m32 nodes
*1. The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be 
       connected to one branch line using multidrop or T-branch connections (sub-branches). 
*2. Number of nodes including Repeater Units

Restrictions (at Baud Rate of 1.5 Mbps)

Cable typeMaximum length 
per segment 
(maximum 
length with 
Repeater Units)
Branch
line 
length
Total 
branch line 
length per
segment
Branch 
location 
restrictions
Maximum
number of 
nodes per 
branch *1
Sub- 
branch
line 
length
Total sub-
branch line 
length per
segment
Maximum
number 
of Slave 
Units per 
segment *2
Round
cable I
Without 
branches
100 m (300 m)0 m *30 m *3----32 nodes
With 
branches
30 m (90 m)2.5 m25 m3 branches/m3 nodes0 m0 m32 nodes
Flat Cable I and 
Flat Cable II 
Round Cable II
30 m (90 m)2.5 m25 m3 branches/m3 nodes0.1 m *42 m *432 nodes
*1. The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be 
       connected to one branch line using multidrop or T-branch connections (sub-branches). 
*2. Number of nodes including Repeater Units 
*3. T-branches cannot be connected (only multidrop connections are possible). 
*4. T-branch connections from sub-branch lines.

Restrictions (at Baud Rate of 93.75 kbps)

Cable typeMaximum length 
per segment 
(maximum 
length with 
Repeater Units)
Branch
line 
length
Total 
branch line 
length per 
segment
Branch 
location 
restrictions
Maximum
number of 
nodes per 
branch *1
Sub- 
branch
line 
length
Total sub- 
branch line 
length per 
segment
Maximum 
number 
of Slave 
Units per 
segment *2
Round cable I500 m (1500 m)6 m120 m3 branches/m1 node--32 nodes
Flat Cable I 
and Flat Cable II 
Round Cable II
No restrictions to a total length per segment of 200 m32 nodes
*1. The maximum number of nodes per branch is the maximum number of Slave Units or Repeater Units that can be 
       connected to one branch line using multidrop or T-branch connections (sub-branches). 
*2. Number of nodes including Repeater Units

Specifications

ModelCJ1W-CRM21
Applicable ControllersNJ *1 /CJ Series
Unit classificationCJ-series Special I/O Unit
Current consumption (Power
supplied from Power Supply 
Unit)
400 mA max.at 5 VDC
Communications power supply 
connector
One communications power supply connector for Slave Units and Repeater Units on the trunk line 
when using Flat Cable *2
Communications power supply 
connector allowable current 
capacity
5 A max.
Maximum number of mountable 
Master Units
One word number assigned:40 Units 
Two word numbers assigned:40 Units 
Four word numbers assigned:24 Units 
Eight word numbers assigned:12 Units
Mounting locationAccording to NJ/CJ-series Special I/O Unit specifications.
Communications power ON/OFF 
monitoring
The ON/OFF status of the communications power supply can be detected at the communications 
power supply connector.
Data stored in Master Unit 
(built-in EEPROM)
1)The following device parameters: 
Registration Table 
Registration Table Check Type 
Registered Slave Unit Participation Monitoring Time,Registered Slave Unit Participation Standby 
Mode,and Event Disable Setting 
Software Settings Table 
Communications Error Communications Stop Mode 
Communications Error Input Data Zero Clear Mode 
Network settings 
2)Part of error history (depends on type of error; mainly serious error related to communications 
stopping)
Noise immunityConforms to IEC 61000-4-4 2 kV (applied to power supply).
Vibration resistance10 to 61.2 Hz with single-amplitude of 0.1 mm,61.2 to 150 Hz and 14.7 m/s2 in X,Y,and Z
directions for 80 min each (sweep time of 8 min × 10 sweeps =80 min)
Shock resistance196 m/s2 (3 times each in X,Y,and Z directions)
Dielectric strength1,000 VAC for 1 min,Leakage current:1 mA max. 
Between communications connector or external current supply connector and GR terminal on 
Power Supply Unit 
Between communications connector or external current supply connector and all Unit connectors
Insulation resistance20 MΩ min.(between isolated circuits)
Ambient operating temperature0 to 55°C
Ambient operating humidity10 to 90%(no condensation)
Ambient operating atmosphereNo corrosive gases
Storage temperature-20 to 75°C
Weight130 g max.(Master Unit only)
*1. Supported only by the CPU Units with unit version 1.01 or later and the Sysmac Studio version 1.02 or higher. 
*2. The Master Unit does not required communications power.

Tidak ada komentar:

Posting Komentar