Jual PLC Omron, PLC Mitsubishi, Inverter Omron, HMI Omron, HMI Weintek

PLC , HMI , INVERTER & SERVO : OMRON , MITSUBISHI , WEINTEK / WEINVIEW , DELTA , LS/LG , INVERTER DANFOSS , PRO-FACE , EMERSON , SHIHLIN ELECTRIC , SLANVERT , etc

Gedung LTC-Glodok Lantai 1 Blok B25 No.5 JAKARTA

Alamat Perwakilan Glodok: Gedung LTC-Glodok Lantai 1 Blok B25 No.5 , JAKARTA

Rabu, 25 Mei 2016

Spesifications CJ1W-INT01

CJ1W-INT01 Interrupt Input Unit (16 Points)

Name16-point Interrupt Input Unit with Terminal Block
ModelCJ1W-INT01
Rated Input Voltage24 VDC
Rated Input Voltage Range20.4 to 26.4 VDC
Input Impedance3.3 kΩ
Input Current7 mA typical (at 24 VDC)
ON Voltage/ON Current14.4 VDC min./3 mA min.
OFF Voltage/OFF Current5 VDC max./1 mA max.
ON Response Time0.05 ms max.
OFF Response Time0.5 ms max.
Number of Circuits16 (16 points/common, 1 circuit)
Number of Simultaneously 
ON Points
100% (16 points/common) simultaneously ON (24 VDC)
Insulation Resistance20 MΩ between external terminals and GR terminal (at 100 VDC)
DielectrQic Strength1,000 VAC between external terminals and GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current 
Consumption
80 mA max.
Weight110 g max.
AccessoriesNone
Circuit Configuration
Up to two Interrupt Input Units can be mounted to the 
CPU Rack. They must be connected as one of the five 
Units immediately next to the CPU Unit. If an Interrupt 
Input Unit is connected in any other position, an Incorrect 
Unit/Expansion Rack Connection error will occur. 
Set the pulse width of signals input to the Interrupt Input 
Unit so they satisfy the following conditions. 
The signal names of the terminals are the device variable 
names. 
The device variable names are the names that use "Jxx" 
as the device name.
External connection and 
terminal-device variable 
diagram
 
The polarity can be connected in either direction. 
The signal names of the terminals are the device variable names. The device variable names are the names 
that use "Jxx" as the device name.
Note: With NJ-series Controllers, Interrupt Input Units can be used as normal Basic Input Units. 
          They cannot be used to start I/O interrupt tasks. 
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. 
   They are not printed on the Units.

Tidak ada komentar:

Posting Komentar