CJ-series Quick-response Input Units CJ1W-IDP01

Capture Input Signals Shorter Than the Cycle Time. This unit is available for CJ/NJ controller.

A pulse width (ON time) of 0.05 ms min. can be read by the Quick-response Input Unit.
Input data read by the internal circuits is cleared when inputs are refreshed.
Quick-response Input Units can be used when communicating with inspection equipment to read the many pulse signals that are too short to be read with normal I/O Units

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL(Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.

Quick-response Input Unit

Unit type: CJ1 Basic I/O Units
No. of words allocated: 1 word
Standards: UC1, N, L, CE
Product
name
SpecificationsCurrent
consumption (A)
Model
I/O pointsInput voltage
current
CommonsInput pulse width
conditions
External
connection
5 V24 V
Quick-
response
Input Unit
16 inputs24 VDC, 7 mA16 points,
1 common
ON time: 0.05 ms max.
OFF time: 0.5 ms max.
Removable
terminal block
0.08---CJ1W-IDP01
Note: There are no restrictions on the mounting position or number of Units.

Accessories

There is no accessory for the CJ series Quick-response Input Units.

CJ1W-IDP01 Quick-response Input Unit (16 Points)

Name16-point Quick-response Input Unit with Terminal Block
ModelCJ1W-IDP01
Rated Input Voltage24 VDC
Rated Input Voltage Range20.4 to 26.4 VDC
Input Impedance3.3 kΩ
Input Current7 mA typical (at 24 VDC)
ON Voltage/ON Current14.4 VDC min./3 mA min.
OFF Voltage/OFF Current5 VDC max./1 mA max.
ON Response Time0.05 ms max.
OFF Response Time0.5 ms max.
Number of Circuits16 (16 points/common, 1 circuit)
Number of Simultaneously 
ON Points
100% (16 points/common) simultaneously ON (24 VDC)
Insulation Resistance20 MΩ between external terminals and GR terminal (at 100 VDC)
Dielectric Strength1,000 VAC between external terminals and GR terminal for 1 minute at a leakage current of 
10 mA max.
Internal Current 
Consumption
80 mA max.
Weight110 g max.
AccessoriesNone
Circuit Configuration
 
The signal names of the terminals are the device 
variable names. 
The device variable names are the names that use 
"Jxx" as the device name.
External connection and 
terminal-device variable 
diagram
 
The input power supply polarity can be connected in either direction. 
The signal names of the terminals are the device variable names. 
The device variable names are the names that use "Jxx" as the device name.
  • With quick-response inputs, pulse inputs shorter than the CPU Unit's cycle time can be read by the CPU Unit.
  • The pulse width (ON time) that can be read by the Quick-response Input Unit is 0.05 ms.
  • Inputs read by the internal circuits are cleared when inputs are refreshed.
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. 
  They are not printed on the Units.

8-point/16-point Units (18-point Terminal Blocks)
CJ1W-IDP01

CJ1W-IDP01 Dimensions 2 CJ1W-IDP01_Dim