PLC FP7



FP7 CPU

  • Equipped with a large memory capacity (up to 220k program steps or up to 500k data words) and a high-speed processor (11ns/step)
  • Local & remote connectivity
    The standard CPU boards with Ethernet interface offer connectivity without limits, from remote programming to monitoring and data logging to FTP server, MEWTOCOL (client/server), EtherNet/IP  and Modbus TCP. Together with the Mini-USB and the RS232C port, it is possible to connect up to 272 devices. Supported services include FTP client/server (file exchange), HTTP Client (data exchange / services with a HTTP server / cloud), and sending e-mails with attachments.
    The integrated web server allows access to the variables of the system / program or diagnostic information using a predefined page or a user-defined page created with the graphical tool "Web Creator" based on HTML5 technology. HTML pages can be viewed from any Internet browser even from mobile devices (smartphones and tablets).
  • Security & reliability
    Built-in program backup. Production can resume in the event of fault. Original program is immediately to hand.
  • Traceability
    Operational and program editing events are logged. Automatic logs of program download and upload are useful, especially for program debugging.
  • Maintenance
    Hour meter operation. The built-in clock/calendar function can be adjusted via Ethernet.
     
ItemSpecifications
AFP7CPS21AFP7CPS31AFP7CPS31EAFP7CPS41E
Power supply, input/outputPower supply24V DC or FP power supply unit
Input12–24V DC, 24V DC (sink/source)
OutputRelay: 2–5A, transistor: 0.1–0.5A (varies with different models)
PerformanceNumber of inputs/outputs10244096
ExpansionUp to 16 unitsUp to 64 units
Operation speed14ns/step11ns/step (for basic instuctions)
Program memoryBuilt-in flash ROM (no backup battery required)
Max. program capacity 64k steps120k steps196k steps
Operation 
memory
Internal relays32,768
Timer (T)4,096 points: 1–4,294,967,295 (in units of 10μs, 1ms, 10ms, 100ms or 1s)
Counter (C)1,024 points: 1–4,294,967,295
Ethernet function--Integrated (MEWTOCOL, Modbus TCP, EtherNet/IP)
Constant scanAvailable (0–125ms)
Clock/calendar functionBuilt-in
 Note: AFP7CPS31S, AFP7CPS41S and AFP7CPS41ES additionally support the encryption function.

Communication cassettes

Product nameSpecificationsProduct number
FP7 communication cassettesRS232C, 1 channel (insulated) AFP7CCS1
RS232C, 2 channels (insulated) AFP7CCS2
RS422 or RS485, 1 channel (insulated) AFP7CCM1
RS422 or RS485, 2 channels (insulated) AFP7CCM2
RS232C, 1 channel (insulated) and RS485, 1 channel (insulated) AFP7CCS1M1
Ethernet 100Base-TX/10Base-TAFP7CCET1

Application cassettes

Product nameSpecificationsProduct number
FP7 application cassettes2-channel analog input 0–10V/0–5V/0–20mA, resolution 12 bit, conversion speed 1ms/channel (non-insulated)AFP7FCAD2
2-channel analog input 0-5V/0-10V/0-20mA, resolution 12 bit, conversion speed 1ms/channel (non-insulated);
1-channel analog output 0-10V/0-20mA
AFP7FCA21
2-channel thermocouple input, K/J type, resolution 0.1°C, conversion speed 100ms/2 channels (insulated)AFP7FCTC2

Input, output and mixed I/O units

Product nameTypeNumber of pointsConnection methodSpecificationsProduct number
FP7 digital input unitDC input16Terminal block12 to 24 V DC, configurable input time constantAFP7X16DW
32MIL connector24V DC, configurable input time constantAFP7X32D2
64MIL connector24V DC, configurable input time constantAFP7X64D2
FP7 digital output unitRelay output16Terminal blockRelay, 2A/point, 5A/common, 16 points/commonAFP7Y16R
Transistor output, sink (NPN)16Terminal blockLoad current 1.0 A, 5A/common, 16 points/commonAFP7Y16T
32MIL connectorLoad current 0.3A, 3.2 A/common, 32 points/commonAFP7Y32T
64MIL connectorLoad current 0.3A/0.1A, 3.2A/common, 32 points/commonAFP7Y64T
Transistor output, source (PNP)16Terminal blockLoad current 1.0A, 5A/common, 16 points/commonAFP7Y16P
32MIL connectorLoad current 0.3 A, 3.2 A/common, 32 points/commonAFP7Y32P
64MIL connectorLoad current 0.3A/0.1A, 3.2A/common, 32 points/commonAFP7Y64P
FP7 digital mixed I/O unitDC input, transistor output, sink (NPN)Input: 32
Output: 32
MIL connectorInput: 24V DC, 32 points/common
Output: load current 0.3A/0.1A, 3.2A/common, 32 points/common
AFP7XY64D2T
DC input, transistor output, source (PNP)Input: 32
Output: 32
MIL connectorInput: 24V DC, 32 points/common
Output: load current 0.3A/0.1A, 3.2A/common, 32 points/common
AFP7XY64D2P

Multi I/O

Product nameSpecificationsProduct Number
FP7 multi input/output unit
  • DC input: Max. 16
  • High-speed counter: Max. 4 channels (4 outputs per channel)
  • Interrupt input: Max. 8
  • Transistor output: Max. 16
  • Pulse output: Max. 4 channels (4 outputs per channel)
  • PWM output: Max. 4 channels (4 outputs per channel)
  • Comparison output: Max. 8
AFP7MXY32DWD
FP7 multi input/output unit  (positioning type)
  • Max. 4 channels for positioning (trapezoidal control with acceleration / deceleration)
AFP7MXY32DWDH

Analog input and output units

Product nameNumber of channelsSpecificationsProduct number
FP7 analog output unit4
Voltage/current, conversion rate 25μs/channel, resolution max. 16 bit,
accuracy max. ±0.05% F.S. (at 25°C)
AFP7DA4H
FP7 analog input unit
Voltage/current, conversion rate 25μs/channel, resolution max. 16 bit,
accuracy max. ±0.05% F.S. (at 25°C)
AFP7AD4H
FP7 analog input unit8
Voltage/current, conversion rate 25μs/channel, resolution max. 16 bit,
accuracy max. ±0.1% F.S. (at 25°C)
AFP7AD8

Thermocouple & RTD units

Multiple types of thermocouples and RTD supported
  • Ten types of thermocouples (K, J, T, N, R, S, B, E, PLII and WRe5-26) are supported. They can be used in combination with voltage and current inputs. 
  • Three types of RTDs (Pt100, JPt100 and Pt1000) are supported for each channel. 
  • Sensor types can be set in the programming software or by a user program. 

SpecificationsProduct number
8 channels, analog input, resolution 0.1°C, K, J, T, N, R, S, B, E, typesAFP7TC8
8 channels, analog input, resolution 0.1°C, Pt100/JPt100/Pt1000 AFP7RTD8

High-speed counter unit

Product nameNumber of channelsSpecificationsProduct number
FP7 high-speed counter unit2
16MHz (for two-phase factor 4 input mode)
4MHz (for incremental/decremental input mode)
AFP7HSC2T
4AFP7HSC4T

Motion control units

Product nameSpecificationsProduct Number
FP7 EtherCAT unit16 real axes, 8 virtual axes, 0.5ms control cycleAFP7MC16EC
32 real axes, 16 virtual axes, 1ms control cycleAFP7MC32EC
64 real axes, 32 virtual axes, 2ms control cycleAFP7MC64EC

Positioning units

SpecificationsProduct number
Output typeNumber of axes controlledMax. operation speedFunctions
Transistor2 (independent)1–500kppsElectronic gear and cam function, linear interpolation, circular interpolationAFP7PP02T
4 (independent)AFP7PP04T
Line driver2 (independent)1–4 MppsAFP7PP02L
4 (independent)AFP7PP04L

Pulse output units

SpecificationsProduct number
Output typeNumber of axes controlledMax. operation speedFunctions
Transistor2 (independent)1–500kppsLinear acceleration, S-shaped acceleration and deceleration control AFP7PG02T
4 (independent)AFP7PG04T
Line driver2 (independent)1–4 MppsAFP7PG02L
4 (independent)AFP7PG04L

Serial communication unit

Product nameSpecificationsProduct number
FP7 serial communication unitFor 2 serial communication cassettes, max. 8 units can be installed per CPUAFP7NSC

Expansion units

Product nameDescriptionProduct number
FP7 expansion master unitUp to 3 slave units can be connected to one expansion master unitAFP7EXPM
FP7 expansion slave unitUp to 16 I/O units and intelligent units can be connected to one expansion slave unitAFP7EXPS

Fieldbus Master Units (FMU)

The FP7 expansion Fieldbus Master Units (FMU) enables manufacturer-independent communication at field level. The units are available for four bus systems: PROFINET; PROFIBUS, DeviceNet and CANopen. For each network type, ready-made function libraries are available for the programming software Control FPWIN Pro. These libraries drastically shorten the time needed to develop your applications, and consequently save valuable human resource costs.
Part number:
AFP7NPFBM
AFP7NDNM
AFP7NCANM
AFP7NPFNM

    Lighting control system

    Use the FP7 together with an Eco-POWER METER such as KW2G and a wireless unit to gather data from exterior lighting systems and monitor energy consumption. Data can be logged and visualized remotely on an office PC with the FP Data Analyzer software.
    • Remote control of the FP7 with a PC
    • Data logging with SD card
    • Easy monitoring of the complete lighting system
    • Wireless systems reduce installation costs

    Analog control (high-speed temperature control)

    Use an impulse heat controller with high-speed PID control for applications such as thermo-compression bonding, thermal welding, etc.
    • Conversion of thermocouple input to achieve highspeed PID control with high precision
    • High-speed analog sampling of 25μ/s
    • High precision with linearity of ±0.05% F.S.

    Visualization of energy consumption in manufacturing plants

    Use the FP7 and Web Datalogger unit to monitor the energy consumption of each part in a plant.
    • Electricity data can be collected at various Locations
    • Multiple Web Datalogger units can be accessed simultaneously
    • CPU communication with 16 locations simultaneously via LAN
    • Create flexible Excel sheets for energy monitoring with the Data Analyzer
    • Measurement data can be stored on SD card

    Monitoring energy consumption of buildings

    Use the FP7 together with an Eco-Power Meter to monitor the energy consumption of each floor in a building.
    • Ability to visualize and monitor the energy consumption (lighting, air conditioning, etc.) of each floor.
    • Only one CPU necessary thanks to the FP7’s big program capacity and the LAN port available
    • Measurement data can be stored on SD card

    Product downloads

    CAD

    DescriptionRelease dateFile sizeLanguage
    FP7 communication and application cassette, 3D Data133 KB
    FP7 CPU, 3D Data854 KB
    FP7 input and output units, positioning units 2axes, 3D Data162 KB
    FP7 input and output units, positioning units 4axes, 3D Data170 KB
    FP7 input, output and mixed io units, 3D Data278 KB
    FP7 master unit, 3D Data196 KB
    FP7 power suppy, 3D Data364 KB
    FP7 serial communication and expansion units, 3D Data571 KB
    FP7 thermocouple & RTD units, 3D Data224 KB

    Cable drawings

    DescriptionRelease dateFile sizeLanguage
    Communication cable between GT terminals and FP Series Tool port, 2m2007-05-0136 KBEnglish

    Data sheets

    DescriptionRelease dateFile sizeLanguage
    Data sheet FP72017-07-132.79 MBEnglish
    Data sheet MF40MD-I, Connector screw terminal 40 pins2018-08-01345 KBEnglish

    Flyers

    DescriptionRelease dateFile sizeLanguage
    Let‘s Start IoT! Idea Book2016-09-012.62 MBEnglish
    Panasonic & EPLAN: A strong cooperation for global engineering795 KBEnglish

    Libraries

    DescriptionRelease dateFile sizeLanguage
    Ethernet Client function library for FP7CPS31ES, FP7CPS31E, FP7CPS41E, FP7CPS41ES.2018-04-10826 KBEnglish
    Fieldbus Master Units (FMU) Profibus, Profinet, CANopen and DeviceNet for FP7. Libraries, Samples and Docu V. 1.0.1.0 (for the use in FPWIN Pro 7).2018-07-034.34 MBEnglish
    Motion - & Communication Library for MINAS A6 Series, Modbus RTU, Version 2.0.4.0, Included Demo Program. Supported PLCs: FP0R, FP-Sigma, FPX, FP7, FP0H2017-12-123.96 MBEnglish
    Motion - & Communication Library for MINAS BL Series, RS485 Serial Protocol, Version 1.5.0.0, Included Demo Program. Supported PLCs: FP-Sigma, FPX, FP72017-12-128.75 MBEnglish
    Motion -& Communication Library for MINAS A5 / A6 Series, Pulse Output Control with Multi I/O Unit, Version 1.0.0.0, Included Demo Program. Supported PLCs: FP72017-12-123.76 MBEnglish
    Motion -& Communication Library for MINAS A5 / A6 Series, Pulse Output Control with Positioning Unit, Version 1.5.0.0, Included Demo Program. Supported PLCs: FP72017-12-122.81 MBEnglish
    Motion -& Communication Library for MINAS A5B/A6B Series, EtherCAT,Version 1.0, Included Demo Program. Supported PLCs: FP72018-02-121.79 MBEnglish
    Motion Control Library for MINAS LIQI / A5 / A6 Series, Pulse Output Control with compact PLCs, Version 1.0, Included Demo Program. Supported PLCs: FP0R, FP-Sigma, FPX, FP72017-12-121.26 MBEnglish
    PEW_A5_A6_RS232 Library2015-04-283.44 MBEnglish

    Manuals

    DescriptionRelease dateFile sizeLanguage
    FP Series Programming Manual2011-08-018.7 MBEnglish
    FP7 Analog Cassette User's Manual, WUME-FP7CA-012014-03-01711 KBEnglish
    FP7 Analog Input Unit User's Manual, WUME-FP7AIH-032016-04-012.01 MBEnglish
    FP7 Analog Input Units User's Manual, ACGM0703V1.3EN2016-03-161.58 MBEnglish
    FP7 Analog Output Unit Technical Manual, ACGM0702V1EN2015-08-011008 KBEnglish
    FP7 Analog Output Unit User's Manual, WUME-FP7AOH-012014-03-011.04 MBEnglish
    FP7 COM Port Communication User's Manual, WUME-FP7COM-012014-03-012.15 MBEnglish
    FP7 Communication Cassette (Ethernet) User's Manual, WUME-FP7CCET-012013-12-011.59 MBEnglish
    FP7 CPU Hardware Manual (PIDSX version), WUME-FP7CPUH-052014-08-014.51 MBEnglish
    FP7 CPU Hardware User's Manual (FPWIN Pro), ACGM0701V1.1EN2014-09-011.96 MBEnglish
    FP7 CPU Unit Logging Trace Function User's Manual, WUME-FP7CPULOG2013-12-011.56 MBEnglish
    FP7 CPU Unit Security Functions User's Manual, WUME-FP7CPUSEC2013-12-01866 KBEnglish
    FP7 CPU Unit User's Manual (Ethernet Expansion Function) WUME-FP7CPUETEX-012018-08-203.59 MBEnglish
    FP7 CPU Unit User's Manual (FPWIN GR), WUME-FP7LAN-022018-06-192.15 MBEnglish
    FP7 CPU Unit User's Manual, 160303Web2016-03-163.97 MBEnglish
    FP7 CPU Unit Ver 4.30 Additional Functions, 201608Web2016-08-011.04 MBEnglish
    FP7 CPU V3.20 Additional Functions Manual, 141215Web2016-01-19722 KBEnglish
    FP7 Digital I/O Units User's Manual (FPWIN Pro), ACGM0704V1EN2014-09-011.29 MBEnglish
    FP7 Ethernet Communication Cassette User's Manual, WUME-FP7CCET-012013-12-011.59 MBEnglish
    FP7 Fieldbus Master Units User’s Manual, ACGM0161V10EN2016-03-161.64 MBEnglish
    FP7 Fieldbus Master Units(PROFIBUS DP Master, DeviceNet Master, CANopen Master and PROFINET IO-Controller) User's Manual, ACGM0706V1EN2016-02-161.64 MBEnglish
    FP7 High-Speed Counter Unit User's Manual, WUME-FP7HSC-022014-06-012.73 MBEnglish
    FP7 Motion Control Unit User's Manual, WUME-FP7MCEC-012016-09-017.87 MBEnglish
    FP7 Multi Input/Output Unit User's Manual, WUME-FP7MXY-022016-09-018.04 MBEnglish
    FP7 Multi-wire Link Unit User's Manual-WUME-FP7MW-022018-06-192.69 MBEnglish
    FP7 PHLS System User's Manual, WUME-FP7PHLS-032014-08-012.09 MBEnglish
    FP7 Positioning Unit User's Manual, WUME-FP7POSP-032016-03-169.24 MBEnglish
    FP7 SCU Communication User's Manual, WUME-FP7COM-022013-12-115.34 MBEnglish
    FP7 SCU Communication User's Manual, WUME_FP7COM2013-12-015.28 MBEnglish
    FP7 TC Multi-analog Input Unit, FP7 RTD Input Unit User's Manual, WUME-WUME-FP7TCRTD-032016-12-062.92 MBEnglish
    FP7 Thermocouple and RTD Input Units User’s Manual, ACGM0705V1EN2015-08-011.43 MBEnglish
    FP7 Upgrade Tool Operation Manual591 KBEnglish
    FP7 Web Server Function Manual2015-09-016.9 MBEnglish
    S Link Address Setting Remote Controller SL-VAR1 (CMJEC-SLVAR1)2015-07-13298 KBEnglish
    Web-Server Function Manual corresponding to Web Creator Ver.3.1.0, 160630Web2018-03-1910.94 MBEnglish

    Shortforms

    DescriptionRelease dateFile sizeLanguage
    Short Form Programmable Logic Controllers2016-10-202.47 MBEnglish

    Software

    DescriptionRelease dateFile sizeLanguage
    Control Configurator FM for FP7 Network Configurator including diagnostic functions for FP7 Fieldbus Master Units, 590 MB48 KB
    Control Configurator WD Version 1.74: setting software for Ethernet communication of FP7, Data Logger Light, PV200/500, HL-C21C, GT32T1/703/704, AFPX-COM5, LG-GS, KW2M-A/KW2M-X and KS1.2016-12-015.43 MBEnglish
    Control Motion Integrator(CMI), Version 1.3, FP7 motion control setting tool for EtherCAT unit. For Windows 7/8.x/10. After 60 days of use the software needs the additional USB key unit(dongle) AFPSMTKEY2018-01-2939.1 MBEnglish
    FP Data7 V.1.60. This Windows software communicates with all PLCs. It’s for a data load, save, edit of the PLC internal memory. Export and import in CSV format is possible too. For Windows 7, 8.x and 10.2018-02-2838.08 MBEnglish
    FP7 Communication Cassette, Firmware Update Ver.1.03, AFP7CCET12016-08-29730 KBEnglish
    FP7 CPU EtherNet/IP EDS files2016-06-15276 KB
    FP7 CPU unit Upgrade Tool plus EtherNet/IP EDS files. FP7 firmware version 4.44 for the PLC types AFP7CPS31, AFP7CPS31S, AFP7CPS31E, AFP7CPS31ES, AFP7CPS41E, AFP7CPS41ES. FP7 firmware version 1.44 for the PLC type AFP7CPS212018-05-166.51 MBEnglish
    FPGT Loader (Windows 7/8.x/10), Vers.2.0.1.3, is a utility for up-/downloading data to and from GT panels(GT01, GT02, GT03-E, GT11, GT21, GT05, GT12, GT32) and PLCs(FP0, FP0R, FP7, FP2, FP2SH, FP-Sigma, FP-X, FP-e). FPGT Loader can be used to make true copies of a master GT or a master PLC project to one or more target GTs or PLCs.2018-04-1863.15 MBEnglish
    FPWIN Pro project sample for FP7 AD4H/AD8 to read the analog input sampling buffer.2018-06-0511 KBEnglish
    WEB creation software v. 3.1.2 for the Web server function of FP7 CPU and KW2M-X. Full version. Works only with additional USB dongle (AFPSWCKEY).2017-10-0262.05 MBEnglish
    WEB creation software v. 3.1.2 for the Web server function of FP7 CPU and KW2M-X. Trial version, reduced to create two screens with 5 parts per screen. No runtime limitation.2017-10-0258.96 MBEnglish

    Technical information

    DescriptionRelease dateFile sizeLanguage
    072 Industry 4.0 with OPC UA over the operator panel series HM2018-01-28113 KBEnglish

    Tidak ada komentar:

    Posting Komentar