The new generation DVP-EH3 PLC is the high-end model of the Delta DVP-E series. 
It provides larger program capacity and data registers for more demanding and complex applications. 
Applications 
High-speed 3-axis servo welding machine, high-speed cutting machine, bar feeder, distributed monitor system in production line. 
Specifications 
Excellent Motion Control 
1)        High-speed ulse output: 4sets of 200kHz pulse output (DVP40/48/64/80EH00T3) 
2)        Supports max. 4 hardware 200kHz high-speed counters 
3)        Increases many motion control instructions to meet the applications that require high-speed and high-precision 
4)        positioning control such as labeling machines, packaging machines and printing machines 
5)        Offers linear / arc interpolation motion control 
6)        Provides up to 16 external interrupt pointers 
Complete Program 
1)        Auto backup function to prevent losing programs and data even when the battery runs out 
2)        Second copy function provides a backup for extra insurance in the event that one set of programs and data are damaged 
3)        Up to 4-level password protects your source programs and inlectual property 
Outstanding Operation Performance 
1)        CPU + ASIC dual processors support floating point operations. 
2)        The max. execution speed of basic instructions is able to reach 0.24μs. 
Flexible Function Extension Modules & Cards 
The multiple selections of extension modules and function cards provide analog I/O, temperature measurement,additional single-axis motion control, high-speed counting, 3rd serial communication port and Ethernet communication card are available. 
PLC-Link 
C-Link allows the user to link up a max. 32 units to the network without having to install extra communication extension modules. 
Brand-New High-Speed Extension Modules 
The brand-new extension modules greatly shorten the data transmission time among the PLC and its extension modules as well as enhance the efficiency of the PLC program. 
Built-in 4 Hardware High-Speed Counters 
Standard  
 | 
Hardware high-speed counter  
 | ||||||
1 phase 1  
 | 
1 phase 1  
 | 
1 phase 2  
 | 
2 phase 2  
 | ||||
sets  
 | 
bandwidth  
 | 
sets  
 | 
bandwidth  
 | 
sets  
 | 
bandwidth  
 | 
sets  
 | 
bandwidth  
 | 
8  
 | 
10KHz  
 | 
4  
 | 
200KHz/20KHz  
 | 
2/2  
 | 
200KHz/20KHz  
 | 
2/2  
 | 
200KHz/20KHz  
 | 
Electrical Specifications 
Model  
Items  
 | 
16EH  
00_3  
 | 
20EH  
00_3  
 | 
32EH  
00_3  
 | 
32EH  
00M3  
 | 
40EH  
00_3  
 | 
48EH  
00_3  
 | 
64EH  
00_3  
 | 
80EH  
00_3  
 | |
Power supply  
voltage  
 | 
100 ~ 240VAC (-15% ~ 10%); 50/60Hz + - 5%  
 | ||||||||
Fuse capacity  
 | 
2A/250VAC  
 | ||||||||
Power  
consumption  
 | 
50VA  
 | 
60VA  
 | 
80VA  
 | ||||||
DC24V current  
output  
 | 
500mA  
 | ||||||||
Power supply  
 | 
DC24V output short circuit  
 | ||||||||
Voltage  
withstand  
 | 
1,500VAC (Primary-secondary), 1,500VAC (Primary-PE),  
500VAC (Secondary-PE)  
 | ||||||||
Insulation  
resistance  
 | 
> 5M Ohm at 500VDC (between all I/O points and ground)  
 | ||||||||
Noise immunity  
 | 
ESD: 8KV Air Discharge  
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V  
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV, RS: 26MHz ~  
1GHz, 10V/m  
 | ||||||||
Grounding  
 | 
The diameter of grounding wire shall not be less than that of L, N terminal of  
the power supply. (When many PLCs are in use at the same time, please  
make sure every PLC is properly grounded.)  
 | ||||||||
Operation/  
storage  
 | 
Operation: 0 °C ~55 °C (temperature), 50~95% (humidity), pollution degree 2  
Storage: -25 °C ~70 °C (temperature), 5~95% (humidity)  
 | ||||||||
Vibration/shock  
resistance  
 | 
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 &  
IEC 68-2-27 (TEST Ea)  
 | ||||||||
Weight (g)  
 | 
R  
 | 
500  
 | 
520  
 | 
652  
 | 
644  
 | 
710  
 | 
748  
 | 
836  
 | 
948  
 | 
T  
 | 
480  
 | 
500  
 | 
612  
 | 
675  
 | 
688  
 | 
756  
 | 
848  
 | ||
Input Point  
 | ||||||
Spec  
Items  
 | 
Two Differential  
inputs (200kHz)  
 | 
24VDC single common port input  
 | ||||
200kHz  
 | 
20kHz  
 | 
Normal input  
 | ||||
Input wiring type  
 | 
Independent  
wiring  
 | 
Change wiring from S/S to SINK or SOURCE  
 | ||||
Input indicator  
 | 
LED display; light on = ON, light off = OFF  
 | |||||
Input voltage (+ - 10%)  
 | 
5~24VDC  
 | 
24VDC  
 | ||||
Input point configuration  
 | 
#1  
 | 
#2  
 | 
#3  
 | 
#4  
 | 
#5  
 | |
Input impedance  
 | 
4.7K Ohm  
 | 
3.3K Ohm  
 | 
3.3K Ohm  
 | 
4.7K Ohm  
 | 
4.7K Ohm  
 | |
Active Level  
 | 
OffàOn  
 | 
> 1mA (5V)  
 | 
> 2mA (15V)  
 | |||
OnàOff  
 | 
< 0.4mA (2V)  
 | 
< 0.5mA (5V)  
 | ||||
Responsetime #5  
 | 
OffàOn  
 | 
< 150ns  
 | 
< 150ns  
 | 
< 3.5us  
 | 
< 8us  
 | 
< 10ms  
 | 
OnàOff  
 | 
< 3us  
 | 
< 3us  
 | 
< 20us  
 | 
< 60us  
 | 
< 20ms  
 | |
Output Point  
 | ||||||
           Spec  
Items  
 | 
Two  
differential  
outputs  
 | 
Single common port  
transistor output  
 | 
Single common port  
relay output  
 | |||
Low speed  
 | 
High speed  
 | 
Normal  
output  
 | ||||
Max. frequency  
 | 
200kHz  
 | 
10kHz  
 | 
200kHz  
 | 
Load ON/OFF control  
 | ||
Minimum load  
 | 
/  
 | 
2mA/DC power  
 | ||||
Working voltage  
 | 
5VDC  
 | 
5 ~ 30VDC  
 | 
< 250VAC, 30VDC  
 | |||
Insulation  
 | 
Line Driver  
 | 
Photo coupler isolation  
 | 
Magnetic isolation  
 | |||
Maximum  
load  
 | 
Resistive  
 | 
< 25mA  
 | 
0.5A/1 point (4A/COM)  
 | 
2A/1 point (5A/COM)  
 | ||
Inductive  
 | 
/  
 | 
12W (24VDC)  
 | 
#1  
 | |||
Lamp  
 | 
/  
 | 
2W(24VDC)  
 | 
20WDC/100WAC  
 | |||
Max. output response  
time  
 | 
0.2us  
 | 
0.2us  
 | 
OffàOn: 20us  
OnàOff: 30us  
 | 
10ms  
 | ||

Profil produk & Dimensi