Inverter Omron Selection Guide
Inverter Selection Guide Item Model 3G3JX 3G3MX2 3G3RX Appearance Power supply and capacity Three-phase 200 V 0.2 to 7.5 kW 0.1 to 15 kW 0.4 to 55 kW Single-phase/three-phase 200 V 0.2 to 2.2 kW 0.1 to 2.2 kW None Three-phase 400 V 0.4 to 7.5 kW 0.4 to 15 kW 0.4 to 132 kW Control method V/f control • • • Sensorless vector control • • Vector control with a PG • Input/output No. of multi-function I/O points • 5 inputs • 1 transistor output • 1 relay output • 7 inputs • 2 transistor outputs • 1 relay output • 9 inputs (1 RUN (FWD) input + 8 multi-function inputs) • 5 transistor outputs • 1 relay output Analog I/O • 1 input (0 to 10 V, 4 to 20 mA) • 1 output (0 to 10 V) ...