CJ Series Temperature Control Unit CJ1W-TC

International Standards

  • The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
  • Contact your OMRON representative for further details and applicable conditions for these standards.
Unit
classi-
fica-
tion
Product
name
SpecificationsNo. of
unit
numbers
allocated
Current
consumption
(A)
ModelStand-
ards
No. of loopsTemperature
sensor inputs
Control outputs5 V24 V
CJ1
Special
I/O
Units
Temperature
Control
Units
4 loopsThermocouple
input
(R, S, K, J, T,
B, L)
Open collector NPN
outputs (pulses)
20.25-CJ1W-TC001 *UC1, N,
L, CE
4 loopsOpen collector PNP
outputs (pulses)
0.25-CJ1W-TC002 *
2 loops, heater
burnout detection
function
Open collector NPN
outputs (pulses)
0.25-CJ1W-TC003
2 loops, heater
burnout detection
function
Open collector PNP
outputs (pulses)
0.25-CJ1W-TC004
4 loopsPlatinum
resistance
thermometer
input
(JPt100, Pt100)
Open collector NPN
outputs (pulses)
0.25-CJ1W-TC101 *
4 loopsOpen collector PNP
outputs (pulses)
0.25-CJ1W-TC102 *
2 loops, heater
burnout detection
function
Open collector NPN
outputs (pulses)
0.25-CJ1W-TC103
2 loops, heater
burnout detection
function
Open collector PNP
outputs (pulses)
0.25-CJ1W-TC104
* This unit cannot be used, with the Machine Automation Controller NJ-series.

General Specifications

ItemSpecification
Unit classificationCJ-series Special I/O Unit
Compatible RacksCJ-series CPU Rack or CJ-series Expansion Rack
Max. number of
Units
10 Units/Rack max. (CPU Rack or Expansion Rack)
CPU Unit data
areas for data
storage/exchange
Special I/O Unit Area
(960 words)
CIO 2000 to CIO 2959
20 words/Unit for
constant data
exchange (6 output
words and 14
input words)
CPU Unit to
Temperature
Control Unit
Set point (SP)
Operating commands
RUN/STOP control
Start/Stop AT
Write commands
Heater burnout set value
Temperature
Control Unit
to CPU Unit
Process value (PV)
Set point (SP)
Status
Heater current monitor
DM words allocated to
Special I/O Units
(9,600 words)
D20000 to D29599
10 words/Unit
transferred when
power is turned ON or
Unit is restarted
CPU Unit to
Temperature
Control Unit
Alarm mode
Alarm hysteresis
90 words/Unit for regular
data exchange
Two-way
transfer
between CPU
Unit and
Temperature
Control Unit
Alarm value
Input compensation value
Control period
Hysteresis
Proportional band
Integral time
Derivative time
Output monitor
Insulation
resistance
20 M Ω min. (at 500 VDC) between the following points:
All output and NC terminals and external AC terminals (Power Supply Unit)
All input terminals and external AC terminals (Power Supply Unit)
All input terminals and all output terminals
All external DC terminals (inputs, outputs, and NC) and the FG plate
Between input terminals (sensor and CT inputs)
I/O terminals and NC terminals
Dielectric strength2,000 VAC 50/60 Hz for 1 min., detected current: 1 mA
The output terminals/NC terminals and external AC terminals (Power Supply Unit)
1,000 VAC 50/60 Hz for 1 min., detected current: 1 mA
Input terminals and external AC terminals (Power Supply Unit)
Input terminals and output terminals
External DC terminals (inputs, outputs, and NC) and the FG plate
500 VAC 50/60 Hz for 1 min., detected current: 1 mA
Between input terminals (sensor and CT inputs)
I/O terminals and NC terminals
Internal current
consumption
250 mA max., 5 VDC
OtherOther general specifications conform to the CJ-series general specifications.
Dimensions31 × 90 × 65 mm (W × H × D)
Weight150 g max.

Characteristics

ItemSpecification
Model numberCJ1W-TC00[]CJ1W-TC10[]
Temperature sensorThermocouple: R, S, K, J, T, L, BPlatinum resistance thermometer: Pt100, JPt100
Number of loops4 loops or 2 loops with heater burnout detection *1
Control output
and heater burnout
alarm output
NPN or PNP outputs, both with short-circuit protection *1
External power supply voltage: 24 VDC +10%, -15%
Max. switching capacity: 100 mA (per output)
Leakage current: 0.3 mA max.
Residual voltage: 3 V max.
Temperature
control method
ON/OFF control or PID control with two degrees of freedom (Set with pin 6 on the Unit's DIP switch.)
Control operationForward or reverse operation (Set with pins 4 and 5 on the Unit's DIP switch.)
RUN/STOP controlSupported (Controlled from the CPU Unit through bits allocated in the Special I/O Unit area.)
Operation with
CPU Unit in
PROGRAM mode
The Temperature Control Unit can be set to continue operating or stop operating when the CPU Unit is in PROGRAM mode. (Set with pin 1 on the Unit's DIP switch.)
Auto/Manual
switch for
operational output
None
Autotuning (AT)
of PID constant
Supported (Controlled from the CPU Unit through bits allocated in the Special I/O Unit area.)
Indication accuracyCelsius: ± 0.3% of PV or ± 1 ° C (whichever is larger) ± 1 digit max.
Fahrenheit: ± 0.3% of PV or ± 2 ° F (whichever is larger) ± 1 digit max.
L and - 100 ° C or less for K and T are ± 2 ° C ± 1 digit max.
200 ° C or less for R and S is ± 3 ° C ± 1 digit max.
No accuracy is specified for 400 ° C or less for B *2
Celsius: ± 0.3% of PV or ± 0.8 ° C (whichever is larger) ± 1 digit max.
Fahrenheit: ± 0.3% of PV or ± 1.6 ° F (whichever is larger) ± 1 digit max.
Hysteresis (when
using ON/OFF control)
0.0 to 999.9 ° C or ° F (0.1 ° C or ° F units)
Proportional band0.1 to 999.9 ° C or ° F (0.1 ° C or ° F units)
Integral (reset) time0 to 9,999 s (one-second units)
Derivative (rate) time0 to 9,999 s (one-second units)
Control period1 to 99 s (one-second units)
Sampling period500 ms (4 loops)
Output refresh period500 ms (4 loops)
Display refresh period500 ms (4 loops)
Input
compensation
value
- 99.9 to 999.9 ° C or ° F (0.1 ° C or ° F units)
Alarm output
setting range
- 999 to 9,999 ° C or ° F (1 ° C or ° F units)
The setting range will be - 99.9 to 999.9 ° C or ° F (0.1 ° C or ° F units) for K or J with decimal point mode, or platinum resistance thermometer.B24
External terminal
connections
Removable terminal block with 18 points (M3 screws)
Effect on the CPU
Unit's cycle time
0.4ms
*1. The last three digits of the model number indicate the Unit's features:
CJ1W-TC Specifications 3
*2. Indication accuracy of thermocouples 
       • Accuracy ratings are given for the Temperature Control Unit used in a set with a cold-junction compensator (on the 
           terminal block). Always use the Unit and terminal block in a set. There are labels with serial numbers attached to 
           the terminal blocks and Units to help keep track of the sets. 
       • When returning a thermocouple-type Temperature Control Unit for repair, always return the Unit and the terminal 
           block (with the cold-junction compensator) as a set.

Heater Burnout (HB) Alarm

ItemSpecification
Maximum heater currentSingle-phase AC, 50 A
Indication accuracy of input current±5% of full scale ± 1 digit max.
Heater burnout alarm setting range0.1 to 49.9 A (0.1 A units)
The heater burnout detection function will not operate if the set value is set to 0.0 A or 50.0 A.
(When the SV is 0.0 A, the heather burnout alarm will be OFF. When the SV is 50.0 A, the heater
burnout alarm will be ON.)
Min. detectable ON time *200 ms
* If the control output is ON for less than 200 ms, the heater burnout detection function will not operate and heater 
   current measurement will not be performed.

Current Transformer (CT) Ratings

ItemE54-CT1E54-CT3
Max. continuous heater current50A120 A *
Dielectric strength1,000 VAC (1 min.)
Vibration resistance50 Hz, 98 m/s2
WeightApprox. 11.5 gApprox. 50 g
AccessoriesNoneContacts (2)
Plugs (2)
Note: Do not use any Current Transformer (CT) other than the OMRON E54-CT1 or E54-CT3 Current Transformer. 
* The maximum continuous heater current that can be detected at a CJ1W-TC[][][] Temperature Control Unit is 50 A.



Senin, 06 Juni 2016

Inverter 3G3MX2

Interpreting Model Numbers

3G3MX2-V1 Lineup 1

3G3MX2 Inverter Models

Note: Inverters with model numbers ending in "-V1" are designed to be used in areas other than China and Europe. 
           Refer to the above "Interpreting Model Numbers" for the model numbers for China and Europe.
Rated voltageEnclosure ratingsMax. applicable motor capacityModel
CT: Heavy loadVT: Light load
3-phase 200 VACIP200.1 kW0.2 kW3G3MX2-A2001-V1
0.2 kW0.4 kW3G3MX2-A2002-V1
0.4 kW0.75 kW3G3MX2-A2004-V1
0.75 kW1.1 kW3G3MX2-A2007-V1
1.5 kW2.2 kW3G3MX2-A2015-V1
2.2 kW3.0 kW3G3MX2-A2022-V1
3.7 kW5.5 kW3G3MX2-A2037-V1
5.5 kW7.5 kW3G3MX2-A2055-V1
7.5 kW11 kW3G3MX2-A2075-V1
11 kW15 kW3G3MX2-A2110-V1
15 kW18.5 kW3G3MX2-A2150-V1
3-phase 400 VACIP200.4 kW0.75 kW3G3MX2-A4004-V1
0.75 kW1.5 kW3G3MX2-A4007-V1
1.5 kW2.2 kW3G3MX2-A4015-V1
2.2 kW3.0 kW3G3MX2-A4022-V1
3.0 kW4.0 kW3G3MX2-A4030-V1
4.0 kW5.5 kW3G3MX2-A4040-V1
5.5 kW7.5 kW3G3MX2-A4055-V1
7.5 kW11 kW3G3MX2-A4075-V1
11 kW15 kW3G3MX2-A4110-V1
15 kW18.5 kW3G3MX2-A4150-V1
0.1 kW0.2 kW3G3MX2-AB001-V1
1-phase 200 VACIP200.2 kW0.4 kW3G3MX2-AB002-V1
0.4 kW0.55 kW3G3MX2-AB004-V1
0.75 kW1.1 kW3G3MX2-AB007-V1
1.5 kW2.2 kW3G3MX2-AB015-V1
2.2 kW3.0 kW3G3MX2-AB022-V1

Communication Unit

NameModel
EtherCAT Communication Unit3G3AX-MX2-ECT
CompoNet Communication Unit3G3AX-MX2-CRT-E
DeviceNet Communication Unit3G3AX-MX2-DRT-E

Related Options

NameSpecificationsModel
Regenerative 
Braking Units
3-phase 200 VACGeneral purpose with Braking resistor3G3AX-RBU21
High Regeneration purpose with Braking resistor3G3AX-RBU22
3-phase 400 VACGeneral purpose with Braking resistor3G3AX-RBU41
Braking ResistorCompact typeResistor 120 W, 180 Ω3G3AX-RBA1201
Resistor 120 W, 100 Ω3G3AX-RBA1202
Resistor 120 W, 5 Ω3G3AX-RBA1203
Resistor 120 W, 35 Ω3G3AX-RBA1204
Standard typeResistor 200 W, 180 Ω3G3AX-RBB2001
Resistor 200 W, 100 Ω3G3AX-RBB2002
Resistor 300 W, 50 Ω3G3AX-RBB3001
Resistor 400 W, 35 Ω3G3AX-RBB4001
Medium capacity typeResistor 400 W, 50 Ω3G3AX-RBC4001
Resistor 600 W, 35 Ω3G3AX-RBC6001
Resistor 1200 W, 17 Ω3G3AX-RBC12001

Regenerative Braking Unit and Braking Resistor Combination

InverterUsage 
conditions
Regenerative 
braking unit
Braking resistorCon-
nec- 
tion 
con- 
figu- 
ra- 
tion
Restrictions
Volt- 
age
Max. 
appli- 
cable 
motor 
ca- 
pacity
(kW)
Model%ED 
*1 
(%)
Ap- 
proxi- 
mate 
braking
torque 
(% *2)
ModelNum-
ber 
of 
units
ModelNum-
ber 
of 
units
Allowa- 
ble 
contin- 
uous 
braking
time 
(s)
Min. 
con- 
nect- 
able 
resis- 
tance 
(Ω)
200-V
Class
0.13G3MX2- 
A2001-V1
3G3MX2- 
AB001-V1
3.0%220%Built-in 
Inverter
3G3AX-RBA12011120100
10.0%220%3G3AX-RBB20011130100
0.23G3MX2- 
A2002-V1
3G3MX2- 
AB002-V1
3.0%220%Built-in 
Inverter
3G3AX-RBA12011120100
10.0%220%3G3AX-RBB20011130100
0.43G3MX2- 
A2004-V1
3G3MX2- 
AB004-V1
3.0%220%Built-in 
Inverter
3G3AX-RBA12011120100
10.0%220%3G3AX-RBB20011130100
0.753G3MX2- 
A2007-V1
3G3MX2- 
AB007-V1
3.0%120%Built-in 
Inverter
3G3AX-RBA1201112050
10.0%120%3G3AX-RBB2001113050
1.53G3MX2- 
A2015-V1
3G3MX2- 
AB015-V1
2.5%110%Built-in 
Inverter
3G3AX-RBA1202111250
10.0%215%3G3AX-RBC4001111050
2.23G3MX2- 
A2022-V1
3G3MX2- 
AB022-V1
3.0%150%Built-in 
Inverter
3G3AX-RBB3001113035
10.0%150%3G3AX-RBC4001111035
3.73G3MX2- 
A2037-V1
3.0%125%Built-in 
Inverter
3G3AX-RBB4001112035
10.0%125%3G3AX-RBC6001111035
5.53G3MX2- 
A2055-V1
3.0%120%Built-in 
Inverter
3G3AX-RBB3001223020
10.0%120%3G3AX-RBC4001221020
7.53G3MX2- 
A2075-V1
3.0%125%Built-in 
Inverter
3G3AX-RBB4001222017
10.0%125%3G3AX-RBC6001221017
113G3MX2- 
A2110-V1
3.0%90%Built-in 
Inverter
3G3AX-RBC12001111017
10.0%90%3G3AX-RBC12001111017
10.0%125%3G3AX-
RBU23 
*3
13G3AX-RBC6001314104
153G3MX2- 
A2150-V1
3.0%110%Built-in 
Inverter
3G3AX-RBB3001573010
10.0%110%3G3AX-RBC4001571010
400-V
Class
0.43G3MX2- 
A4004-V1
3.0%220%Built-in 
Inverter
3G3AX-RBA12012320180
10.0%220%3G3AX-RBB20012330180
0.753G3MX2- 
A4007-V1
3.0%220%Built-in 
Inverter
3G3AX-RBA12012320180
10.0%220%3G3AX-RBB20012330180
1.53G3MX2- 
A4015-V1
3.0%120%Built-in 
Inverter
3G3AX-RBA12012320180
10.0%120%3G3AX-RBB20012330180
2.23G3MX2- 
A4022-V1
2.5%150%Built-in 
Inverter
3G3AX-RBA12022312100
10.0%220%3G3AX-RBC40012310100
3.03G3MX2- 
A4030-V1
2.5%110%Built-in 
Inverter
3G3AX-RBA12022312100
10.0%215%3G3AX-RBC40012310100
4.03G3MX2- 
A4040-V1
3.0%165%Built-in 
Inverter
3G3AX-RBB30012330100
10.0%165%3G3AX-RBC40012310100
5.53G3MX2- 
A4055-V1
3.0%120%Built-in 
Inverter
3G3AX-RBB3001233070
10.0%120%3G3AX-RBC4001231070
7.53G3MX2- 
A4075-V1
3.0%125%Built-in 
Inverter
3G3AX-RBB4001232070
10.0%125%3G3AX-RBC6001231070
113G3MX2- 
A4110-V1
3.0%85%Built-in 
Inverter
3G3AX-RBB4001232070
10.0%85%3G3AX-RBC6001231070
10.0%120%3G3AX-
RBU41 
*3
13G3AX-RBC40014151034
153G3MX2- 
A4150-V1
3.0%125%Built-in 
Inverter
3G3AX-RBB4001452035
10.0%125%3G3AX-RBC6001451035
*1 %ED shows the ratio that can be used for braking (deceleration time) among operating time of one task period. 
*2 Approximate breaking torque is shown in % of rating torque of the motor (100%). 
*3 Please remove the built-in resistor.
NameSpecifications of InverterModel
Voltage classCT: Heavy loadVT: Light load
Radio Noise Filter3-phase 200 VAC0.1 kW0.2 kW3G3AX-ZCL2
0.2 kW0.4 kW
0.4 kW0.75 kW
0.75 kW1.1 kW
1.5 kW2.2 kW
2.2 kW3.0 kW
3.7 kW5.5 kW3G3AX-ZCL1 (3G3AX-ZCL2)
5.5 kW7.5 kW
7.5 kW11 kW3G3AX-ZCL1
11 kW15 kW
15 kW18.5 kW
1-phase 200 VAC0.1 kW0.2 kW3G3AX-ZCL2
0.2 kW0.4 kW
0.4 kW0.55 kW
0.75 kW1.1 kW
1.5 kW2.2 kW
2.2 kW3.0 kW
3-phase 400 VAC0.4 kW0.75 kW3G3AX-ZCL2 (3G3AX-ZCL1)
0.75 kW1.5 kW
1.5 kW2.2 kW
2.2 kW3.0 kW
3.0 kW4.0 kW
4.0 kW5.5 kW
5.5 kW7.5 kW
7.5 kW11 kW3G3AX-ZCL1
11 kW15 kW
15 kW18.5 kW
Input Noise Filter3-phase 200 VAC0.1 kW0.2 kW3G3AX-NFI21
0.2 kW0.4 kW
0.4 kW0.75 kW
0.75 kW1.1 kW3G3AX-NFI22
1.5 kW2.2 kW3G3AX-NFI23
2.2 kW3.0 kW
3.7 kW5.5 kW3G3AX-NFI24
5.5 kW7.5 kW3G3AX-NFI25
7.5 kW11 kW3G3AX-NFI26
11 kW15 kW3G3AX-NFI27
15 kW18.5 kW3G3AX-NFI28
1-phase 200 VAC0.1 kW0.2 kW3G3AX-NFI21
0.2 kW0.4 kW
0.4 kW0.55 kW3G3AX-NFI22
0.75 kW1.1 kW3G3AX-NFI23
1.5 kW2.2 kW3G3AX-NFI23 *
2.2 kW3.0 kW3G3AX-NFI24
3-phase 400 VAC0.4 kW0.75 kW3G3AX-NFI41
0.75 kW1.5 kW
1.5 kW2.2 kW
2.2 kW3.0 kW3G3AX-NFI42
3.0 kW4.0 kW
4.0 kW5.5 kW3G3AX-NFI43
5.5 kW7.5 kW
7.5 kW11 kW3G3AX-NFI44
11 kW15 kW3G3AX-NFI45
15 kW18.5 kW3G3AX-NFI46
Output Noise Filter3-phase 200 VAC0.1 kW0.2 kW3G3AX-NFO01
0.2 kW0.4 kW
0.4 kW0.75 kW
0.75 kW1.1 kW3G3AX-NFO02
1.5 kW2.2 kW
2.2 kW3.0 kW3G3AX-NFO03
3.7 kW5.5 kW
5.5 kW7.5 kW3G3AX-NFO04
7.5 kW11 kW
11 kW15 kW3G3AX-NFO05
15 kW18.5 kW3G3AX-NFO06
1-phase 200 VAC0.1 kW0.2 kW3G3AX-NFO01
0.2 kW0.4 kW
0.4 kW0.55 kW3G3AX-NFO02
0.75 kW1.1 kW
1.5 kW2.2 kW3G3AX-NFO03
2.2 kW3.0 kW
3-phase 400 VAC0.4 kW0.75 kW3G3AX-NFO01
0.75 kW1.5 kW
1.5 kW2.2 kW3G3AX-NFO02
2.2 kW3.0 kW
3.0 kW4.0 kW
4.0 kW5.5 kW3G3AX-NFO03
5.5 kW7.5 kW
7.5 kW11 kW
11 kW15 kW3G3AX-NFO04
15 kW18.5 kW
DC Reactor3-phase 200 VAC0.1 kW0.2 kW3G3AX-DL2002
0.2 kW0.4 kW3G3AX-DL2004
0.4 kW0.75 kW3G3AX-DL2007
0.75 kW1.1 kW3G3AX-DL2015
1.5 kW2.2 kW3G3AX-DL2022
2.2 kW3.0 kW3G3AX-DL2037
3.7 kW5.5 kW3G3AX-DL2055
5.5 kW7.5 kW3G3AX-DL2075
7.5 kW11 kW3G3AX-DL2110
11 kW15 kW3G3AX-DL2150
15 kW18.5 kW3G3AX-DL2220
1-phase 200 VAC0.1 kW0.2 kW3G3AX-DL2002
0.2 kW0.4 kW3G3AX-DL2004
0.4 kW0.55 kW3G3AX-DL2007
0.75 kW1.1 kW3G3AX-DL2015
1.5 kW2.2 kW3G3AX-DL2022
2.2 kW3.0 kW3G3AX-DL2037
3-phase 400 VAC0.4 kW0.75 kW3G3AX-DL4007
0.75 kW1.5 kW3G3AX-DL4015 *
1.5 kW2.2 kW3G3AX-DL4022
2.2 kW3.0 kW3G3AX-DL4037
3.0 kW4.0 kW
4.0 kW5.5 kW3G3AX-DL4055
5.5 kW7.5 kW3G3AX-DL4075 *
7.5 kW11 kW3G3AX-DL4110 *
11 kW15 kW3G3AX-DL4150
15 kW18.5 kW3G3AX-DL4220
AC Reactor3-phase 200 VAC0.1 kW0.2 kW3G3AX-AL2025
0.2 kW0.4 kW
0.4 kW0.75 kW
0.75 kW1.1 kW
1.5 kW2.2 kW3G3AX-AL2055
2.2 kW3.0 kW
3.7 kW5.5 kW3G3AX-AL2110
5.5 kW7.5 kW3G3AX-AL2110 *
7.5 kW11 kW3G3AX-AL2220
11 kW15 kW3G3AX-AL2220 *
15 kW18.5 kW3G3AX-AL2330
1-phase 200 VAC0.1 kW0.2 kW3G3AX-AL2025
0.2 kW0.4 kW
0.4 kW0.55 kW
0.75 kW1.1 kW
1.5 kW2.2 kW3G3AX-AL2055 *
2.2 kW3.0 kW3G3AX-AL2110
3-phase 400 VAC0.4 kW0.75 kW3G3AX-AL4025
0.75 kW1.5 kW
1.5 kW2.2 kW3G3AX-AL4055
2.2 kW3.0 kW
3.0 kW4.0 kW
4.0 kW5.5 kW3G3AX-AL4110
5.5 kW7.5 kW3G3AX-AL4110 *
7.5 kW11 kW3G3AX-AL4220
11 kW15 kW3G3AX-AL4220 *
15 kW18.5 kW3G3AX-AL4330
* Only the CT rating is supported. 
Note: When using the Inverter for light load rating, select the model with one size larger capacity (rated current).
NameCable length (m)Model
Digital Operator-3G3AX-OP01
Connection cable1 m3G3AX-OPCN1
3 m3G3AX-OPCN3

Recommended EtherCAT Communications Cables

Use Straight STP (shielded twisted-pair) cable of category 5 or higher with double shielding (braiding and aluminum foil tape) for EtherCAT.

Cabel with Connectors

ItemAppearanceRecommended 
manufacturer
Cable 
length (m)
Model
Standard type 
Cable with Connectors on Both 
Ends (RJ45/RJ45) 
Wire Gauge and Number of Pairs: 
AWG27, 4-pair Cable 
Cable Sheath material: LSZH *2 
Cable color: Yellow *3
3164_lu_8_1OMRON0.3XS6W-6LSZH8SS30CM-Y
0.5XS6W-6LSZH8SS50CM-Y
1XS6W-6LSZH8SS100CM-Y
2XS6W-6LSZH8SS200CM-Y
3XS6W-6LSZH8SS300CM-Y
5XS6W-6LSZH8SS500CM-Y
Rugged type 
Cable with Connectors on Both 
Ends (RJ45/RJ45) 
Wire Gauge and Number of Pairs: 
AWG22, 2-pair Cable
3164_lu_8_2OMRON0.3XS5W-T421-AMD-K
0.5XS5W-T421-BMD-K
1XS5W-T421-CMD-K
2XS5W-T421-DMD-K
5XS5W-T421-GMD-K
10XS5W-T421-JMD-K
Rugged type 
Cable with Connectors on Both 
Ends (M12 Straight/RJ45) 
Wire Gauge and Number of Pairs: 
AWG22, 2-pair Cable
3164_lu_8_3OMRON0.3XS5W-T421-AMC-K
0.5XS5W-T421-BMC-K
1XS5W-T421-CMC-K
2XS5W-T421-DMC-K
5XS5W-T421-GMC-K
10XS5W-T421-JMC-K
Rugged type 
Cable with Connectors on Both 
Ends (M12 Right-angle/RJ45) 
Wire Gauge and Number of Pairs: 
AWG22, 2-pair Cable
3164_lu_8_4OMRON0.3XS5W-T422-AMC-K
0.5XS5W-T422-BMC-K
1XS5W-T422-CMC-K
2XS5W-T422-DMC-K
5XS5W-T422-GMC-K
10XS5W-T422-JMC-K
*1 Standard type cables length 0.2, 0.3, 0.5, 1, 1.5, 2, 3, 5, 7.5, 10, 15 and 20m are available. 
      Rugged type cables length 0.3, 0.5, 1, 2, 3, 5, 10 and 15m are available. 
*2 The lineup features Low Smoke Zero Halogen cables for in-cabinet use and PUR cables for out-of-cabinet use. 
*3 Cables colors are available in blue, yellow, or Green 
Note: For details, refer to Cat.No.G019.

Cables/Connectors

Wire Gauge and Number of Pairs: AWG24, 4-pair Cable

ItemAppearanceRecommended manufacturerModel
Cables---Hitachi Metals, Ltd.NETSTAR-C5E SAB 0.5 x 4P *
---Kuramo Electric Co.KETH-SB *
---SWCC Showa Cable Systems Co.FAE-5004 *
RJ45 Connectors---Panduit CorporationMPS588-C *
* We recommend you to use above cable and connector together.

Wire Gauge and Number of Pairs: AWG22, 2-pair Cable

ItemAppearanceRecommended manufacturerModel
Cables---Kuramo Electric Co.KETH-PSB-OMR *
---JMACS Japan Co., Ltd.PNET/B *
RJ45 Assembly Connector
3164_lu_10_1
OMRONXS6G-T421-1 *
* We recommend you to use above cable and connector together. 
Note: Connect both ends of cable shielded wires to the connector hoods.

Software

How to Select Required Support Software for Your Controller

The required Support Software depends on the Controller to connect. Please check the following table when purchasing the Support Software.
ItemOmron PLC SystemOmron Machine Automation Controller System
ControllerCS, CJ, CP, and other seriesNJ/NX-series
InverterInverter MX2-series V1 type 
Inverter MX2-series V1 type with EtherCAT 
Communication Unit 
(Applicable to the CJ series only.) 
Inverter MX2-series V1 type with CompoNet 
Communication Unit 
Inverter MX2-series V1 type with DeviceNet 
Communication Unit
Inverter MX2-series V1 type 
Inverter MX2-series V1 type with EtherCAT Communication 
Unit 
Inverter MX2-series V1 type with CompoNet Communication 
Unit 
Inverter MX2-series V1 type with DeviceNet Communication 
Unit
SoftwareFA Integrated Tool Package CX-OneAutomation Software Sysmac Studio

FA Integrated Tool Package CX-One

Product 
name
SpecificationsModelStand- 
ards
Number of 
licenses
Media
FA Integrated 
Tool Package 
CX-One 
Ver.4.[]
The CX-One is a comprehensive software 
package that integrates Support Software 
for OMRON PLCs and components. 

CX-One runs on following OS. 
Windows XP (Service Pack 3 or higher, 
32-bit version)/ 
Windows Vista (32-bit/64-bit version)/ 
Windows 7 (32-bit/64-bit version)/ 
Windows 8 (32-bit/64-bit version)/ 
Windows 8.1 (32-bit/64-bit version)/ 
Windows 10 (32-bit/64-bit version) 

CX-One Version.4.[] includes CX-Drive Ver.2.[]. 
For details, refer to the CX-One catalog 
(Cat. No. R134)
1 license 
*
DVDCXONE-AL01D-V4-
* Multi licenses (3, 10, 30, or 50 licenses) and DVD media without licenses are also available for the CX-One.

Automation Software Sysmac Studio

Please purchase a DVD and required number of licenses the first time you purchase the Sysmac Studio. DVDs and licenses are available individually. Each model of licenses does not include any DVD.
Product 
name
SpecificationsModelStand- 
ards
Number of 
licenses
Media
Sysmac 
Studio 
Standard 
Edition 
Ver.1.[][]
The Sysmac Studio provides an integrated 
development environment to set up, program, debug, 
and maintain NJ/NX-series Controllers and other 
Machine Automation Controllers, as well as EtherCAT 
slaves. 

Sysmac Studio runs on the following OS. 
Windows XP (Service Pack 3 or higher, 32-bit 
version)/Windows Vista (32-bit version)/Windows 7 
(32-bit/64-bit version)/Windows 8 (32-bit/64-bit 
version)/Windows 8.1 (32-bit/64-bit version)/ 
Windows 10 (32-bit/64-bit version) 

The Sysmac Studio Standard Edition DVD includes 
Support Software to set up EtherNet/IP Units, 
DeviceNet slaves, Serial Communications Units, and 
Support Software for creating screens on HMIs (CX- 
Designer). 
For details, refer to the Sysmac Integrated Catalogue 
(P072).

(Media only)
DVDSYSMAC-SE200D-
1 license 
*
---SYSMAC-SE201L-
* Multi licenses are available for the Sysmac Studio (3, 10, 30, or 50 licenses).